Check Of Limit Density; Installing Distribution Joint - Sanyo R410A Installation Instructions Manual

W-3way eco-i system air conditioner
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

WARNING

1-11. Check of Limit Density

When installing an air conditioner in a room, it is necessary
to ensure that even if the refrigerant gas accidentally leaks
out, its density does not exceed the limit level for that room.

1-12. Installing Distribution Joint

CAUTION
(1) Refer to "HOW TO ATTACH DISTRIBUTION JOINT"
enclosed with the optional distribution joint kit
(APR-CHRZP900BAB, RZP224BAB, RZP680BAB,
RZP1350BAB).
(2) When creating a branch using a commercially available
T-joint (header joint system), orient the main tubing so
that it is either horizontal (level) or vertical. In order to
prevent accumulation of refrigerant oil in stopped units,
if the main tubing is horizontal then each branch tubing
length should be at an angle that is greater than horizon-
tal. If the main tubing is vertical, provide a raised starting
portion for each branch.
[Header joint system]
Be sure to solidly weld shut the T-joint end (marked
by "X" in the figure). In addition, pay attention to the
insertion depth of each connected tube so that the
flow of refrigerant within the T-joint is not impeded.
When using the header joint system, do not make fur-
ther branches in the tubing.
Do not use the header joint system on the outdoor
unit side.
(3) If there are height differences between indoor units or if
branch tubing that follows a distribution joint is connect-
ed to only 1 unit, a trap or ball valve must be added to
that distribution joint. (When adding the ball valve, locate
it within 15 - 3/4" of the distribution joint.)
If a trap or ball valve is not added, do not operate the
system before repairs to a malfunctioning unit are
completed. (The refrigerant oil sent through the tub-
ing to the malfunctioning unit will accumulate and
may damage the compressor.)
Always check the gas density
limit for the room in which the
unit is installed.
Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrig-
erant gas is heavier than air.
Tube branching methods (horizontal use)
Header joint system (Indoor)
Outdoor
Indoor
Horizontal
line
L3 6.56 ft.
Types of vertical trap specifications
(When using ball valve)
Main tubing
Ball valve
(BV: purchased
separately)
Indoor unit (1)
(When not using ball valve)
Main tubing
Branch tubing is
directed upward.
Indoor unit is directed downward
12
B
Horizontal
A
A
line
View as seen
B
from arrow
Arrow view
Install at a
positive angle
Indoor
Install at a
positive angle
(15 – 30°)
Indoor
Solidly welded
Horizontal
line
shut (X)
Indoor unit (more than 2 units)
(If only 1 unit is connected, a ball valve
is also needed on this side.)
Horizontal
Indoor unit
(Each unit is connected
to tubing that is either
level or is directed
downward.)
More than
7–7/8"