Danfoss C67 User Manual page 57

Ecl comfort
Table of Contents

Advertisement

Service parameter(s) 37-41
37 Time constant for return temperature limitation
Circuit
(I) / (II)
Controls how fast the actual return temperature adapts to the
desired return temperature limitation.
Adjust the time constant for the return limitation.
The setting will eliminate the difference
between the acceptable and the actual return
temperature.
The difference is integrated to adjust the desired
flow temperature.
OFF: The desired flow temperature will not be
1:
50:
40 DHW pump post-run
Circuit
(I) / (II)
The DHW pump can continue to run after charging to utilize the
remaining heat in the heat exchanger / boiler.
0:
1 ... 9: The time the DHW pump runs after the
This function also prevents that too DHW is
circulated in the heating circuit.
41 DHW charging pump post-run (P5)
Circuit
I
Set the post-run time of the DHW charging pump in the
secondary circuit. The settings only apply to heating system types
5 and 5a in section 10.
0:
1 ... 9: The time the pump runs after the charging
When the DHW charging pump runs after the charging of
the DHW tank has stopped, the heat in the exchanger can be
utilized to a better extent.
The post-run of the DHW charging pump (line 41) should not be
set to a shorter time than that of the DHW pump (line 40).
Setting range
OFF / 1 ... 50
adjusted any further.
The desired flow temperature will be
adjusted quickly.
The desired flow temperature will be
adjusted slowly.
Setting range
0 ... 9 min.
The DHW pump stops immediately after
charging.
charging has ended.
Setting range
0 ... 9 min.
The pump stops immediately after
charging.
has ended.
32k
Factory setting
(25) / (25)
Factory setting
(0) / (0) min.
Factory setting
0 min.
The grey
side of the
ECL Card