Napoleon HDX40NT Installation And Operating Instructions Manual page 9

Natural gas / propane
Table of Contents

Advertisement

9
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify
that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must
not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run
is 20 feet. The maximum allowable vertical vent length is 40 feet. The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0" rise per foot however for optimum performance it is recommended that all horizontal
runs have a minimum 1/4" rise per foot using fl exible venting. For safe and proper operation of the appliance, follow
the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family
dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" air gap
all around between the inner liner and outer liner is required for safe operation.
8.3
W415-0869 / A / 06.10.10