Carrier 50ZH Series Product Data page 8

3-phase single-packaged 2-1/2 to 5 tons
Table of Contents

Advertisement

Base unit dimensions—50ZH060
UNIT
50ZH060
8
ELECTRICAL
CHARACTERISTICS
V-Ph-Hz
208/230-3-60, 460-3-60
REQUIRED CLEARANCE TO COMBUSTIBLE MA TL.
TOP OF UNIT .........................................................................................0
DUCT SIDE OF UNIT.............................................................................0
SIDE OPPOSITE DUCTS ......................................................................0
BOTTOM OF UNIT .................................................................................0
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
CONDENSER
.
COIL ACCESS SIDE..............................................30.00 [762.0]
POWER ENTRY SIDE....................................................................30.00 [762.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................30.00 [762.0]
LEGEND
NEC – National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge, with the exception of the condenser coil (36.00 in [914.0 mm]. A
removable fence or barricade requires no clearance.
2. Dimensions are in inches. Dimensions in [ ] are in millimeters.
UNIT WEIGHT
CENTER OF GRAVITY mm (in.)
Lb
Kg
X
368
167
356 (14.00)
INCHES [mm]
INCHES [mm]
INCHES [mm]
UNIT HEIGHT
Y
Z
508 (20.00)
406 (16.00)
(IN.)
35.8