INSTALL CLAMPS ON DRAIN TUBE
ATTACH DRAIN TUBE TO CONDENSATE
DRAIN TRAP
PULL DRAIN STUB
THROUGH CASING
OPEN SPRING CLAMP
INSERT FACTORY SUPPLIED 1/2 IN. CPVC
TO 3/4 IN. PVC ADAPTER OR 1/2 IN. CPVC PIPE
*CLAMP MAY BE LOCATED ON OUTSIDE OF DRAIN
TUBE
Fig. 14 - - Formed Rubber Drain Grommet
Fig. 15 - - Modify Rubber Drain Elbow
NOTE: Trap grommet is required only for direct-vent
applications.
A11342A
Fig. 16 - - Horizontal Drain Trap Grommet
Attach elbow to condensate trap
Formed end of
grommet
Connect short end
of "Z" pipe to modified
drain elbow
Factory supplied 1/2 in. CPVC to
3/4 in. PVC adapter
TRAP, DRAIN ELBOW WITH DISCHARGE PIPE
Formed end of grommet
Open spring clamp. Insert
1/2 in. to 3/4 in. CPVC to
PVC adapter or 1/2 in.
CPVC pipe
LEFT SIDE DRAIN ROUTED BEHIND INDUCER
NOTE: Remove Inducer Housing for easier access, if desired.
A11581
Fig. 17 - - Drain Trap Connection and Routing
19
Remove knockout.
Install grommet before
relocating condensate
trap.
Cut formed end off
condensate drain
elbow
Modified drain elbow connect to
condensate trap and "Z" pipe
(Appearance may vary)
A11582
s