Carrier Performance 24APA Installation Instructions Manual page 12

Performance series air conditioner with puronr refrigerant 1-1/2 to 5 nominal tons (size 18 to 60)
Hide thumbs Also See for Performance 24APA:
Table of Contents

Advertisement

STATUS CODES
Table 3 shows the status codes flashed by the amber status light.
Most system problems can be diagnosed by reading the status
code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the
status light. The short flashes indicate the first digit in the status
code, followed by long flashes indicating the second digit of the
error code. The short flash is 0.25 second ON and the long flash
is 1.0 second ON. Time between flashes is 0.25 second. Time
OPERATION
FAULT
Standby – no
call for unit
None
operation
Standby – no
call for unit
None
operation
Cooling
None
Operation
System Communica-
tions Failure
High Pressure
Switch Open
Low Pressure
Switch Open
Control Fault
Brown Out
(24 v)
Outdoor Air Temp
Sensor Fault
Outdoor Coil Sensor
Fault
Thermistors out
of range
Thermal Cutout
Contactor Shorted
No 230V at
Compressor
Thermal Lockout
Low Pressure Lockout
High Pressure
Lockout
between short flash and first long flash is 1.0 second. Time
between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the
appropriate flash code. Table 3 gives possible causes and actions
related to each error.
Example: 3 short flashes followed by 2 long flashes indicates a
32 code. Table 3 shows this to be low pressure switch open.
Table 3— Status Codes
AMBER LED
FLASH CODE
On solid, no flash
Normal operation --- 3 thermostat wires or 4 wire Infinity Control
Normal operation --- No call for cooling with 2--- wire connection or indoor
Off
unit not powered.
1, pause
Normal operation
Communication with user interface lost. Check wiring to UI, indoor and
16
outdoor units
High pressure switch trip. Check refrigerant charge, outdoor fan opera-
31
tion and coils for airflow restrictions.
32
Low pressure switch trip. Check refrigerant charge and indoor air flow
Outdoor unit control board has failed. Control board needs to be
45
replaced.
The control voltage is less than 15.5v for at least 4 seconds. Compressor
46
and fan operation not allowed until control voltage is a minimum of 17.5v.
Verify control voltage.
Outdoor air sensor not reading or out of range. Ohm out sensor and
53
check wiring
55
Coil sensor not reading or out of range. Ohm out sensor and check wiring
Improper relationship between coil sensor and outdoor air sensor. Ohm
56
out sensors and check wiring.
Compressor voltage sensed after start--- up, then absent for 10 consecu-
tive seconds while cooling demand exists. Possible causes are internal
compressor overload trip or loss of high voltage to compressor without
72
loss of control voltage. The control will continue fan operation and wait
15 minutes to attempt a restart. Fault will clear when restart is successful,
or low voltage power is cycled.
Compressor voltage sensed when no demand for compressor operation
73
exists. Contactor may be stuck closed or there is a wiring error.
Compressor voltage not sensed when compressor should be starting.
Disconnect may be open or contactor may be stuck open or there is a
74
wiring error.
Thermal cutout occurs in three consecutive cycles. Unit operation locked
82
out for 4 hours or until 24v power recycled.
Low pressure switch trip has occurred during 5 consecutive cycles. Unit
83
operation locked out for 4 hours or until 24v power recycled.
High pressure switch trip has occurred during 5 consecutive cycles. Unit
84
operation locked out for 4 hours or until 24v power recycled.
12
Possible Cause and Action

Advertisement

Table of Contents
loading

Table of Contents