Service parameters (10-199)

Circuit I
Lines Setting ranges
10 Choice of room panel / remote control
0 ... 5
11 Setback temperature dependent
on outdoor temperature
OFF / -29 ... 10 °C
12 Boost
0 ... 99%
14 Optimizing time constant
OFF / 10 ... 59
15 Adaptive function of room
temperature
OFF / 1 ... 30
20 Optimization based on room /
outdoor temperature
ON / OFF
21 Total stop
ON / OFF
22 Pump exercise
ON / OFF
23 Valve exercise
ON / OFF
24 Gear motor / thermo actuator
ON / OFF
30 Return temperature limitation
10 ... 110 °C
35 Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
36 Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
37 Time constant for return temperature
limitation
OFF / 1 ... 50
52 Closed valve / normal operation
ON / OFF
85 Priority for return temperature
limitation
ON / OFF
141 Override input selection
OFF / 1 ... 4
174 Motor protection
OFF / 10 ... 59 min.
189 Min. activation time, gear motor
2 ... 10
196 Service pin LON
ON / OFF
197 LON reset
ON / OFF
198 Daylight saving time changeover
ON / OFF
199 Master / slave address
0 ... 9, 15
Factory settings
0
-15 °C
0%
OFF
OFF
OFF
OFF
ON
OFF
ON
50 °C
-2.0
0.0
25
OFF
OFF
OFF
OFF
6
OFF
ON
ON
15
31
Your settings
°C
%
°C
min.