Preparing The Mounting Cutout - Siemens SIMATIC Industrial Flat Panel IFP1500 Operating Instructions Manual

Hide thumbs Also See for SIMATIC Industrial Flat Panel IFP1500:
Table of Contents

Advertisement

Installing and connecting the device
3.1 Preparing for installation
3.1.4

Preparing the mounting cutout

Note
Stability of the mounting cutout
The material in the area of the mounting cutout must be sturdy enough to ensure permanent
safe mounting of the device.
The force of the clamps or operation of the device may not lead to deformation of the
material in order to achieve the degrees of protection described below.
Degrees of protection
The various degrees of protection of the device can only be guaranteed if the following
requirements are met:
● To achieve the degree of protection specified in the technical specifications: Material
thickness at the mounting cut-out: 2 mm to 6 mm
● Permitted deviation from plane at the mounting cutout: ≤ 0.5 mm
This condition must also be met for the installed device.
● Permitted surface roughness in the area of the seal: ≤ 120 µm (R
Dimensions of the mounting cutout
Width and height should be reversed accordingly when mounting in vertical format.
30
120)
z
Industrial Flat Panel IFP1500, IFP1900, IFP2200
Operating Instructions, 06/2014, A5E31298376-AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents