MODEL HW-300 BOILER
Input: 300,000 Btuh
Required Connector or Smoke Pipe Diameter
Total Vent Height (Measured in Feet Above Draft Hood)
Connector
10
15
Rise in Feet
1
10
10
2
10
10
3
10
10
4 or more
Total Vent Height (Measured in Feet Above Draft Hood)
Number
Total Input
if Units
10
15
Btuh x 1000
Combined
Manifold and Common Vent Diameter (in Inches)
2
600
14
12
3
900
16
14
4
1200
18
16
MODEL HW-399 BOILER
Input: 399,000 Btuh
Required Connector or Smoke Pipe Diameter
Total Vent Height (Measured in Feet Above Draft Hood)
Connector
10
15
Rise in Feet
1
12
12
2
12
12
3
12
10
4 or more
10
10
Total Vent Height (Measured in Feet Above Draft Hood)
Number
Total Input
if Units
10
15
Btuh x 1000
Combined
Manifold and Common Vent Diameter (in Inches)
2
798
14
14
3
1197
18
16
4
1596
20
20
MODEL HW-420 BOILER
Input: 420,000 Btuh
Required Connector or Smoke Pipe Diameter
Total Vent Height (Measured in Feet Above Draft Hood)
Connector
10
15
Rise in Feet
1
12
12
2
12
12
3
12
10
4 or more
10
10
Total Vent Height (Measured in Feet Above Draft Hood)
Number
Total Input
if Units
10
15
Btuh x 1000
Combined
Manifold and Common Vent Diameter (in Inches)
2
840
14
14
3
1260
18
16
4
1680
20
20
TABLE 14. COMBINED VENT SIZING TABLES
Draft Hood Outlet 8"
20
30
40
50
60
80
Connector Diameter (in Inches)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
30
40
50
60
80
12
12
10
10
10
10
14
14
12
12
12
12
16
14
14
14
14
12
Draft Hood Outlet 10"
20
30
40
50
60
80
Connector Diameter (in Inches)
12
12
12
12
12
12
12
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
30
40
50
60
80
14
12
12
12
12
12
16
14
14
14
14
14
18
16
16
16
14
14
Draft Hood Outlet 10"
20
30
40
50
60
80
Connector Diameter (in Inches)
12
12
12
12
12
12
12
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
30
40
50
60
80
14
12
12
12
12
12
16
14
14
14
14
14
18
16
16
16
14
14
Input: 520,000 Btuh
Required Connector or Smoke Pipe Diameter
Connector
100
Rise in Feet
10
1
10
2
10
3
4 or more
Number
Total Input
100
if Units
Btuh x 1000
Combined
10
2
1040
12
3
1560
12
4
2080
5
2600
6
3120
7
3640
8
4160
Input: 660,000 or 670,000 Btuh
100
Required Connector or Smoke Pipe Diameter
12
Connector
10
Rise in Feet
10
1
10
2
3
100
4 or more
Number
12
Total Input
if Units
12
Btuh x 1000
Combined
14
2
1220
3
1830
4
2440
5
3050
6
3660
7
4270
8
4880
100
9
5490
10
6100
12
11
6710
10
12
7320
10
10
Example: Known: (5) model HW-670 boilers. (See illustration).
100
Connector rise - 2' (Note 1' is minimum). Total vent height 30'.
Problem: Determine diameter of connector, manifold and common
12
vent.
12
14
Procedure: Enter the top of the HW-670 table (total vent
height) at 30' and the side at 2' (connector rise). A 14"
connector diameter is indicated for each connector rise.
To determine the manifold and common vent size, enter table
on this page (total vent height) at 30 and the side at 5 boilers. A
manifold diameter of 24" (610 mm) is indicated.
23
MODEL HW-520 BOILER
Draft Hood Outlet 10"
Total Vent Height (Measured in Feet Above Draft Hood)
10
15
20
30
40
50
Connector Diameter (in Inches)
14
14
14
12
12
12
12
12
12
12
12
12
12
12
12
12
10
10
12
12
12
12
10
10
Total Vent Height (Measured in Feet Above Draft Hood)
10
15
20
30
40
50
Manifold and Common Vent Diameter (in Inches)
16
16
14
14
14
14
20
18
18
16
16
14
22
22
20
18
18
18
26
24
22
20
20
18
28
26
24
22
22
20
30
28
26
24
24
22
32
30
28
26
24
24
MODEL HW-670 BOILER
Draft Hood Outlet 12"
Total Vent Height (Measured in Feet Above Draft Hood)
10
15
20
30
40
50
Connector Diameter (in Inches)
16
14
14
14
14
14
14
14
14
14
14
12
14
14
12
12
12
12
12
12
12
12
12
12
Total Vent Height (Measured in Feet Above Draft Hood)
10
15
20
30
40
50
Manifold and Common Vent Diameter (in Inches)
18
18
16
16
14
14
22
20
20
18
18
16
26
24
22
20
20
18
28
26
26
24
22
22
32
28
28
26
24
24
34
32
30
28
26
24
36
34
32
30
28
26
38
36
34
30
30
28
40
38
36
32
30
30
42
38
38
34
32
30
46
44
40
38
36
34
60
80
100
12
12
12
12
12
12
10
10
10
10
10
10
60
80
100
12
12
12
14
14
14
16
16
14
18
18
18
20
18
18
22
20
20
22
22
20
60
80
100
14
14
14
12
12
12
12
12
12
12
12
12
60
80
100
14
14
14
16
16
14
18
18
16
20
20
18
22
22
20
24
22
22
26
24
24
28
26
24
28
26
26
28
28
26
34
32
30