Carrier 50ZH Product Data page 5

Single-package units 2 to 5 nominal tons
Table of Contents

Advertisement

Base unit dimensions — 50ZH024,030
UNIT
50ZH024
50ZH030
208/230-1-60; 208/230-3-60
ELECTRICAL
CHARACTERISTICS
208/230-1-60
232
254
REQUIRED CLEARANCES TO COMBUSTIBLE MAT'L
Top of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
NEC REQUIRED CLEARANCES
Between Units, Power Entry Side . . . . . . . . . . . . . . . . . 1066.8 (42.00)
Unit and Ungrounded Surfaces, Power Entry Side . . . . . . . 914.0 (36.00)
Unit and Block or Concrete Walls and Other Grounded
Surfaces, Power Entry Side . . . . . . . . . . . . . . . . . . . . 1066.8 (42.00)
REQUIRED CLEARANCES FOR SERVICING
Outdoor Coil Access Side . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)
Power Entry Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)
(Except for NEC Requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914.0 (36.00)
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . 762.0 (30.00)
LEGEND
NEC — National Electrical Code
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge, with the exception of the outdoor coil (914 mm [36 in.]). A
removable fence or barricade requires no clearance.
2. Dimensions are in millimeters. Dimensions in ( ) are in inches.
3.
is the center of gravity.
UNIT WT
Lb
Kg
X
106
356 (14.0)
116
356 (14.0)
CENTER OF GRAVITY mm (in.)
Y
483 (19.0)
305 (12.0)
483 (19.0)
305 (12.0)
Millimeters (in.)
Millimeters (in.)
Millimeters (in.)
Z
5