Performance Data - Carrier 42C Series Product Data

Fan coil air conditioners 50/60 hz 150 to 2000 cfm
Table of Contents

Advertisement

Performance data (cont)
UNIT
AIRFLOW
SIZE
(Cfm)
01
150
300
03
NOTE: Cooling capacity based on standard conditions at 80 F dry bulb,
67 F wet bulb entering air temperature. To determine sensible, use ratio
of 0.83 to above total.
STEAM HEATING CAPACITIES (Btuh)
MODELS 42VA,VB,VF,CA,CE,CF,CG,CH,CK
UNIT SIZE
1-ROW COIL
02
12,270
03
16,890
04
21,940
06
31,610
08
40,415
10
52,685
12
62,355
NOTES:
1. Ratings based on nominal cfm, 70 F entering dry bulb, 2 psig.
2. All capacities above 50,000 Btuh rating are beyond the capacity of
the standard control valve. Consult factory for these applications.
3. Steam coils are not available for 42VC,VE,VG units.
74
COOLING AND HEATING CAPACITIES (Btuh) — MODEL 42VG
PRESSURE
WATER FLOW
(Gpm)
1.0
1.5
2.0
2.5
3.0
1.0
1.5
2.0
2.5
3.0
2-ROW COIL
19,920
28,580
37,530
54,995
71,250
91,655
109,120
COOLING
DROP
(ft wg)
40
0.8
4,240
1.6
4,950
2.7
5,320
3.6
5,500
5.5
5,590
1.5
7,850
2.9
8,850
4.8
10,200
6.4
10,800
9.7
11,100
Entering Water Temperature (F)
45
50
160
3,450
2,750
8,200
4,080
3,270
8,750
4,500
3,500
9,220
4,620
3,620
9,450
4,850
3,770
9,700
6,400
5,100
15,500
7,800
6,250
16,700
8,660
6,730
17,300
9,100
7,130
17,600
9,650
7,500
18,000
HEATING
180
10,000
10,850
11,300
11,700
12,300
18,900
20,400
21,100
21,500
22,000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents