Carrier 58DLA Product Data page 8

Weathermaker 8000 deluxe 4-way multipoise induced-combustion input capacities: 45,000 thru 155,000 btuh
Table of Contents

Advertisement

SEE NOTES: 1,2,4,5,7,8,9
SEE NOTES: 1,2,3,4,7,8,9
SEE NOTES: 1,2,4,7,8,9
UPFLOW
DOWNFLOW
UPFLOW
A02058
A02061
A02059
SEE NOTES:1,2,3,4,5,7,8,9
SEE NOTES: 1,2,4,5,6,7,8,9
SEE NOTES: 1,2,3,4,5,7,8,9
DOWNFLOW
DOWNFLOW
DOWNFLOW
A02063
A02062
A02060
Venting Notes
1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel
Gas Code (NFGC), ANSI Z223.1/NFPA 54. In Canada, latest edition of the National Standards of Canada,
Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1-00.
2. Immediately increase to 5-inch vent connector outside furnace casing when 5-inch vent connector required,
refer to Note 1.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the
furnace, except when KGAVG0101DFG is used in downflow position.
4. Type B vent where required, refer to Note 1.
5. 4" single wall vent must be used inside furnace casing and the KGAVG0101DFG Downflow Vent Guard Kit.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with bottom vent
configuration.
7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kit,
KGACA02014FC and KGACA02015FC for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, space
o
approximately 180
apart.
9. Secure all other single wall vent connector joints with (3) corrosion-resistant screws spaced approximately
o
120
apart. Secure Type B vent connectors per vent connector manufacturer's recommendations.