Carrier 42BH Series Product Data

System fan coil air conditioner 800 to 4000 cfm

Advertisement

Copyright 1990 Carrier Corporation
Product
Data
42BH
System Fan Coil
Air Conditioner
800 to 4000 Cfm
Satisfy All Your Design Requirements
with Carrier's Versatile 42BH Fan
Coil Unit
• A selection of 6 sizes covers capaci-
ties from 800 to 4000 cfm
• Choice of motors, from
eliminates oversizing
• Wide range of coil options for
2-pipe or 4-pipe system
• Optional DX coils with expansion
valve and distributor
Features/Benefits
The 42BH fan coil unit pro-
vides year-round comfort air
conditioning with central
station operating economy.
A variety of coil options
reduces first cost
Four- or 6-row cooling coils combine
the capacities you need with the
most efficient heat transfer surface.
For 4-pipe systems, select either of
two split-coil options. Coils consist of
alu-minum fins securely bonded to
1
-in. OD seamless copper tubes.
2
Each fin's aluminum collar ensures
accurate control of the fin spacing,
while completely covering the tubes to
lengthen coil life. All coils also fea-
ture manual air vents, with automatic
air vent available as an option.
Fan wheels are designed to
provide low operating costs
The forward-curved, centrifugal,
double-inlet fans are statically and
dynamically balanced at the factory to
minimize transmission of vibration
to the building structure.
The belt-driven motor has a variable-
pitch pulley which adjusts at the job-
site to accommodate limited ranges of
air quantities and pressures.
Form 42BH-1PD
1
to 3 hp,
4

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 42BH Series

  • Page 1: Features/Benefits

    • Wide range of coil options for 2-pipe or 4-pipe system • Optional DX coils with expansion valve and distributor Features/Benefits The 42BH fan coil unit pro- vides year-round comfort air conditioning with central station operating economy. A variety of coil options reduces first cost...
  • Page 2: Table Of Contents

    Guide Specifications ..........26 cut installation time and labor ex- pense. Durable construction means easy-to-maintain units The 42BH casings are fabricated from heavy-gage steel, reinforced for maximum rigidity and structural strength. Removable side panels allow Model number nomenclature easy access for servicing interior components.
  • Page 3: Physical Data

    Physical data UNIT SIZE 42BH NOMINAL CFM 1200 1600 2000 3000 4000 SHIPPING WT (lb) APPROX FILTERS Number...Size (in.) 1...16 x 24 1...16 x 33 2...16 x 21 ⁄ 2...20 x 22 2...27 x 22 2...27 x 29 Face Area (sq ft) 10.9...
  • Page 4: Compact, Lightweight Units Are De-Dimensions

    ⁄ hp shipped separately. 4. Unit shown is R.H., L.H. unit is opposite. 5. Motor location varies with unit horsepower. Above ⁄ hp, motors are base mounted. 6. Four-row coil shown. UNIT SIZE 42BH DIMENSION ⁄ ⁄ ⁄ ⁄ ⁄...
  • Page 5: Signed For Easy Mounting. One-In. Selection Procedure

    .00445 x Actual Cfm tors table, page 7, at 1800 cfm and find that a 67.0 42BH size 20 unit has a total heat (TH) factor of = 29.69 − .00445 x 1800 0.94 and a sensible heat (SH) factor of 0.93.
  • Page 6: Selection Procedure

    SH Factor (from Enter the 42BH Cooling Capacity Correction Factors Cooling Capacity table (page 7) at 1800 cfm and find that a 42BH size Correction Factors) 20 unit has a total heat (TH) factor of 0.94 and a sen- x Hot Water Capacity sible heat (SH) factor of 0.93.
  • Page 7: Duct Flanges On Discharge And 2-In. Performance Data

    Performance data 42BH COOLING CAPACITY CORRECTION FACTORS UNIT SIZE 42BH ACTUAL 0.86 0.82 — — — — — — — — — — 0.94 0.91 — — — — — — — — — — 1.00 1.00 — — —...
  • Page 8 DX Sensible Capacity (MBtuh) = Base SH x Sensible Correction Factor % of Nominal Cfm = Actual Cfm (from Fan Performance table) ÷ Nominal Cfm 42BH HOT WATER CAPACITY CORRECTION FACTORS ENTERING WATER TEMPERATURE (F) ENTERING AIR TEMPERATURE (F) 0.455 0.545...
  • Page 9 42BH NOMINAL COOLING CAPACITIES COOLING* UNIT SIZE NOMINAL CFM COIL ROWS Total Capacity Sensible Capacity 42BH (MBtuh) (MBtuh) 33.0 21.2 24.4 17.7 15.0 14.6 39.0 24.7 30.0 21.4 21.0 18.5 10.4 52.0 31.0 39.5 26.0 26.0 22.0 1200 12.6 63.0 37.5...
  • Page 10 Performance data (cont) COOLING CAPACITY 42BH08 4-ROW — 800 CFM 6-ROW — 800 CFM...
  • Page 11 COOLING CAPACITY 42BH12 4-ROW — 1200 CFM 6-ROW — 1200 CFM...
  • Page 12 Performance data (cont) COOLING CAPACITY 42BH16 4-ROW — 1600 CFM 6-ROW — 1600 CFM...
  • Page 13 COOLING CAPACITY 42BH20 4-ROW — 2000 CFM NOTE: Arrows illustrate Step III and IV of Selection Procedure Example 1. 6-ROW — 2000 CFM...
  • Page 14 Performance data (cont) COOLING CAPACITY 42BH30 4-ROW — 3000 CFM 6-ROW — 3000 CFM...
  • Page 15 COOLING CAPACITY 42BH40 4-ROW — 4000 CFM 6-ROW — 4000 CFM...
  • Page 16 DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) 4-ROW COIL ENTERING AIR TEMPERATURE (F) — db/wb CONNECTION UNIT R-22 SIZE (in.) SIZE SUCTION 75/63 80/63 75/67 80/67 80/71 85/71 42BH TEMP Liquid Suction 17.1 13.0 17.8 16.1 21.8 12.0 22.1 15.0 27.0 13.8 27.2 16.9...
  • Page 17 DIRECT EXPANSION (DX) BASE COOLING CAPACITIES* (MBtuh) (cont) 6-ROW COIL ENTERING AIR TEMPERATURE (F) — db/wb CONNECTION UNIT R-22 SIZE (in.) SIZE SUCTION 75/63 80/63 75/67 80/67 80/71 85/71 42BH TEMP Liquid Suction 21.3 15.4 21.8 18.8 26.6 14.3 26.8 17.6 32.3 16.3 32.4 19.6...
  • Page 18 Performance data (cont) 42BH WATER PRESSURE DROP...
  • Page 19 42BH WATER PRESSURE DROP (cont)
  • Page 20 Performance data (cont) 42BH WATER PRESSURE DROP (cont)
  • Page 21 36.74 22.615 37.66 23.22 38.61 23.84 39.57 24.48 40.57 25.12 41.58 25.78 42.62 43.69 42BH COMPONENT STATIC RESISTANCE (in. wg) COOLING COIL HEATING COIL GRILLES FILTER UNIT SIZE CABINET Single Double 4 Row 6 Row 1 Row 2 Row 4 Row...
  • Page 22 Performance data (cont) 42BH FAN PERFORMANCE TOTAL STATIC PRESSURE (in. wg) UNIT SIZE ⁄ ⁄ 1000 ⁄ 1000 ⁄ 1000 ⁄ 1000 ⁄ 1250 ⁄ 1250 ⁄ ⁄ ⁄ 1000 ⁄ 1000 ⁄ 1000 ⁄ 1000 ⁄ 1250 ⁄ 1250 ⁄...
  • Page 23 HEATING CAPACITY CURVES IMPORTANT Unit 42BH standard motors are rated for a maximum ambient air temperature of 104 F when fully loaded. Since these are draw-through units, it will be necessary to calculate the air temperature leaving the coil for all heating applications.
  • Page 24: Performance Data

    Performance data (cont) HEATING CAPACITY CURVES (cont) IMPORTANT Unit 42BH standard motors are rated for a maximum ambient air temperature of 104 F when fully loaded. Since these are draw-through units, it will be necessary to calculate the air temperature leaving the coil for all heating applications.
  • Page 25: Duct Flanges On Return Are Furnished Electrical Data

    Electrical data 60 HZ SINGLE-PHASE MOTORS (1750 Rpm) 50 HZ SINGLE-PHASE MOTORS (1425 Rpm) VOLTAGE VOLTAGE HORSEPOWER HORSEPOWER ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 13.0 ⁄ 13.8 15.0 16.0 50 HZ THREE-PHASE MOTORS (1425 Rpm) 60 HZ THREE-PHASE MOTORS (1750 Rpm) VOLTAGE HORSEPOWER VOLTAGE...
  • Page 26: Standard. These Integral Duct Flanges Guide Specifications

    Certain standard features are not applicable when the the manufacturer’s instructions. features designated by * are specified. See your local Part 2 — Products Carrier Sales Office for amending specifications. 2.01 EQUIPMENT 1. Coils A. General: Unit coil(s) shall be equipped with automatic Factory-assembled, horizontal, draw-thru type fan coil air vent(s).
  • Page 27 Carrier Corporation • Syracuse, New York 13221 5-90 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 3 Page 28 Catalog No. 524-228 Printed in U.S.A. PC 201...