Carrier 50JZ Product Data page 23

Single-package heat pump units with puron (r-410a) refrigerant 2 to 5 nominal tons
Table of Contents

Advertisement

VOLTAGE
UNIT
RANGE
SIZE
V-PH-Hz
50JZ
Min
024
208/230-1-60
187
030
208/230-1-60
187
036
208/230-1-60
187
042
208/230-1-60
187
048
208/230-1-60
187
060
208/230-1-60
187
LEGEND
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v.
If power distribution voltage to unit varies from rated heater voltage,
heater KW will vary accordingly.
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
50JZ WITH ICM FIOP ELECTRICAL DATA
OUTDOOR
COMPRESSOR
FAN MOTOR
Max
RLA
LRA
FLA
253
13.5
61.0
0.9
253
15.9
73.0
0.9
253
16.9
83.0
1.6
253
22.4
105.0
0.9
253
21.3
109.0
1.6
253
27.6
158.0
1.6
®
INDOOR
FAN MOTOR
ELECTRIC HEAT
FLA
Nominal kw*
—/—
3.8/5.0
18.1/20.8
4.3
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
—/—
3.8/5.0
18.1/20.8
4.3
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
—/—
3.8/5.0
18.1/20.8
6.8
5.4/7.2
25.9/30.0
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
—/—
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
6.8
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
—/—
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
6.8
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
—/—
3.8/5.0
18.1/20.8
5.4/7.2
25.9/30.0
9.2
7.5/10.0
36.1/41.7
11.3/15.0
54.2/62.5
15.0/20.0
72.2/83.3
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457
452 = 5 v
(BC) 464
457 = 7 v
(AC) 457
455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
SINGLE POINT
POWER SUPPLY
MAX FUSE
FLA
UNIT MCA
or CKT. BKR.
—/—
22.1/22.1
30/30
44.6/48.1
50/50
54.5/59.6
60/–
67.2/74.2
—/—
25.1/25.1
30/30
47.6/51.1
50/50
57.4/62.6
70.2/77.2
92.8/103.2
—/—
29.5/29.5
40/40
52.1/55.6
60/60
61.9/67.0
74.7/81.6
97.2/107.7
—/—
35.7/35.7
50/50
58.3/61.7
68.1/73.2
80.8/87.8
103.4/113.0
126.0/139.9
—/—
35.0/35.0
50/50
57.6/61.1
67.4/72.5
80.2/87.1
102.7/113.2
125.3/139.2
—/—
45.1/45.1
60/60
67.7/71.1
77.7/82.8
90.3/97.2
112.8/123.2
135.4/149.3
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
7
457
= 1.53%
MOCP
–/70
70/80
70/70
80/80
100/110
70/80
80/90
100/110
70/70
80/80
90/90
110/125
150/150
70/70
80/80
90/90
110/125
150/150
80/80
90/90
100/110
125/125
150/150
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

50jz02450jz03050jz03650jz04250jz04850jz060

Table of Contents