Option 13 - - Room Air Temperature Offset
Selections:
- -5 to 5_ F — Default is 0.
This option selects the number of degrees F to be added to the displayed
temperature to calibrate or deliberately miscalibrate the measured room
temperature.
Option 15 - - Auto Changeover Availability
Selections:
ON — This is default.
OF
ON allows automatic changeover between heating and cooling as demand
requires. OF maintains either heating or cooling mode only. Auto changeover is
not available when PH, PC, H or C is selected under Option 1.
Option 16 - - Maximum Cycles Per Hour
Selections:
2, 4, or 6 — Default is 4.
The maximum cycle rate is limited by internal timers to the selected number of
cycles per hour. Selection of a higher number causes faster cycling resulting in
more constant room temperature.
Option 17 - - Minimum Time Between Equipment Stages
Selections:
10, 15, 20, 25 — Default is 15.
When there are two stages of heat available, this is the amount of time the first
stage must operate before the second stage can turn on. With heat pumps, longer
15