Locate Of Firebox; Minimum Clearances - MHSC Lo-rider LCUF32-R Installation And Operation Instructions Manual

Vent-free fireboxes
Table of Contents

Advertisement

LoCATe FireBox and CLeArANCe reqUireMeNTS

LoCATe oF FireBox

Carefully select the best location for installation of your
vent-free firebox. The following factors should be taken
into consideration:
Clearance to side wall, ceiling, woodwork and windows.
Refer to "Clearances/Height Requirements" on Page 8.
Minimum clearances to combustibles must be main-
tained.
Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
Installation must provide adequate ventilation and com-
bustion air.
do NoT iNSTALL THiS FireBox iN A BedrooM
or BATHrooM.
Location should be out of high traffic or windy or drafty
areas.
do NoT iNSTALL WHere CUrTAiNS, FUrNiTUre,
CLoTHiNG or oTHer FLAMMABLe oBJeCTS Are
LeSS THAN 42" FroM FroNT oF HeATer.
Never obstruct the front opening of the vent-free firebox
or restrict the flow of combustion and ventilation air.
Minimize modifications to existing construction. Refer
to Figure 3 for location suggestions.
Do not install in the vicinity where gasoline or other
flammable liquids may be stored. The vent-free firebox
must be kept clear and free from these combustible
materials.
Figure 3 -
Possible Locations of Firebox
FP2440
fireplace locations
26D4721

MiNiMUM CLeArANCeS

Ensure that minimum clearances shown in Figures 4
through 7 are maintained. Left and right clearances are
determined when facing the front of the firebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
fire hazard.
1. Sidewall clearances: The clearance from the inside
of the appliance to any combustible wall should not be
less than 6". Figure 4
2. Ceiling clearance: The ceiling must be at least 42"
from the top of the firebox opening. Figure 4
3. Back wall clearance: The appliance may be placed
against a combustible back wall.
FP2687
Figure 4 -
Clearance and Height Requirements
4. Floor clearance: This inner chamber firebox floor must
FP2687
be installed at least 1" above any combustible flooring
minimum clearances
material, such as carpeting or asphalt tile, which is
closer than 14" to the base of the firebox. Figure 5
Or
The inner chamber firebox floor may be installed nearer
to the floor if a minimum of 14" of noncombustible ma-
terial such as slate or marble is installed between the
base of the firebox and the combustible flooring. Figure
6
LCUF Vent Free Firebox
4 2
M i
"
n i m
u m
6 "
M i
n i m
u m
6 "
M i
n i m
u m
7