Section A: Pilot light will not light (new installation).
Is the manual gas shut-off valve,
located in the supply line to the
water heater, in the on position?
YES
Have you bled all the air
NO
from the pilot tube and
gas supply line?
YES
Is the igniter producing a
YES
spark?
NO
Follow the "Testing the Igniter
System" section in this manual.
Section B: Pilot light repeatedly goes out.
Remove the burner door
assembly. Are the flame-trap and
burner free from debris due to
excessive lint, dirt, dust or oil?
YES
Does the flame-trap
Reassemble the heater and attempt to
NO
show signs of
return the heater to service. Does the
discoloration?
pilot remain lit?
YES
Shut-off the gas supply to the water heater at
the manual gas shut-off valve, then contact Sears
Service at 1-800-4-MY-HOME
(1-800-469-4663)
®
NO
Go to section C.
PILOT LIGHT TROUBLESHOOTING CHART
Turn the manual gas shut-off valve to
the on position and follow the lighting
NO
instructions on the front of the water heater.
While repeatedly depressing the igniter
button, push in and hold the gas control/
temperature knob until the pilot is lit and
maintains a stable flame, (status light
will blink) then release the gas control/
temperature knob.
Set thermostat to desired temperature.
Refer to the "Maintenance of
your Water Heater" section of this
NO
manual for information on cleaning
the flame-trap and burner.
YES
Set to desired temperature.
Does the diagnostic status light on the
gas control valve/thermostat give
a two flash error code?
YES
Refer to the "Replacing the Pilot/Thermopile
Assembly" instructions in the manual.
Reassemble and restore to service.
Section C: Pilot light will not remain lit.
Check for insufficient combustion air.
Are the combustion air supply and ventilation openings
of sufficient size? See "Combustion Air Supply and
Ventilation" section in this manual for requirements.
YES
NO
Is there a furnace/air handler in the same room as the water heater?
YES
Does the return air duct for the furnace/
air handler draw its air from a separate
location than the water heater? Refer to
the "Installation Instructions" section of
this manual.
YES
Is there proper drafting at the
drafthood? See "Draft Hood
Operation" section of manual.
YES
Contact Sears Service at
1-800-4-MY-HOME
NOTE: If you are still experiencing difficulties after
following the steps in sections A, B, and C,
Sears Service at 1-800-4-MY-HOME
NO
34
NO
Contact a local Heating,
Ventilation, Air-Conditioning
NO
& Refrigeration authorized
service provider to correct
the combustion air supply/
ventilation issue.
Check the vent
system for restrictions/
NO
obstructions and check
the vent termination
height. Refer to the
"Installation Instructions"
section of this manual for
specific requirements.
®
(1-800-469-4663).
(1-800-469-4663).
®
Correct size of
openings to allow
sufficient air.
contact