Chimney Installation - MHSC SB50HB Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

CHIMNey INSTaLLaTION

Figure 17
NOTe: Flue outlet should be two feet above all portions of the building
within ten feet as shown in Figure 17. The chimney must not extend
more than 90 inches above the roof without additional support.
1. Lay out, cut and frame openings through all ceilings and the roof at the point where the chimney
will pass through. Unless the chimney is to be offset, the point where the center line of the chimney
will pass through the ceiling and roof can be determined with a plumb line as shown by Figure
18. The fireplace should be located in the planned installation position. After the center line is
established and a nail is driven to mark the point, the opening can be cut if you are satisfied with
the chimney location relative to ceiling and roof joists and/or any other obstructions. The roof
opening center line should be marked by driving a nail through the roof from underneath that will
penetrate the roof and can be located from the rooftop. If the chimney is to penetrate a pitched
roof, the hole in the roof must be rectangular instead of square and should be sized according
to Table1.
. Install the firestop spacer as required from beneath the ceiling unless the space above is attic
space. In an attic, the firestop spacer should be installed at the floor level of the attic. You must
have joists or headers on all four sides of the spacer and use a minimum of four 8-penny nails
to secure the spacer.
3. To install the chimney sections, insert the male end of the flue, the smallest diameter pipe, into
the flue outlet of the fireplace and press down until the snap locks engage. Continue the process,
adding the chimney sections on top of each other until the chimney is at least six inches above
the roof opening on all sides. As the chimney sections are installed, check each joint to make
sure it is properly locked to the previous section. If additional strength of the outer pipe joints is
desired, you may use two or three sheet metal screws placed through the area where the outer
pipes overlap one another. To install these screws, drill a 1/8-inch diameter hole through the
chimney sections, taking care not to penetrate the inner flue pipe. WarNINg: Be very careful
when drilling the holes into the outer pipe. The drill must not penetrate the inner stainless steel
pipe.
NOTe: If you intend to have a total fireplace installation of more that 30 feet you must use chimney
support model 11CS at or below 30 feet to support the weight of additional chimney pipe.
To install the chimney support, place the crimped end of the flue and outlet air duct portions into the
last section of chimney pipe. Push down until the outside or inlet air duct of the chimney support
overlaps and snap locks the chimney support into the chimney section.
Nail the support straps tightly to a building frame member or ceiling joist as shown by Figure 19.
You must use at least two 8-penny nails per strap.
87D0058
10'
2' Min.
3'
Min.
2' Min.
AC617
RLTSKC8
2/11/98
SB50HB Series Woodburning Fireplace
10'
3'
Min.
AC617
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents