Start-Up Procedure And Adjustment; Operational Checks; Heat Anticipator Setting; Furnace Operation - Amana GUI Installation Instructions Manual

Gas-fired warm air furnace
Table of Contents

Advertisement

XII. STAR
XII. ST
XII. ST
XII. ST
XII. ST
AR
ART T T T T -UP PR
AR
AR
-UP PR
-UP PROCEDURE AND AD
-UP PR
-UP PR
OCEDURE AND ADJUST
OCEDURE AND AD
OCEDURE AND AD
OCEDURE AND AD
Furnace must have a 115 VAC power supply properly connected
and grounded. Proper polarity must be maintained for correct op-
eration. An interlock switch prevents furnace operation if the blower
door is not in place. Keep the blower access door in place except for
inspection and maintenance.
This furnace is also equipped with a self-diagnosing electronic con-
trol module. In the event a furnace component is not operating prop-
erly, the control module LED will flash on and off in a factory-pro-
grammed sequence, depending on the problem encountered. This
light can be viewed through the observation window in the blower
access door. Refer to the Troubleshooting Chart for further explana-
tion of the lighting codes.
On new installations, or if a functional part such as the gas valve,
pressure switch, or limit control has been replaced, verify that the
furnace is operating properly after servicing.
Check furnace operation as outlined in the following instructions. If
any sparking, odors, or unusual noises are encountered, shut off
electrical power and recheck for wiring errors, or obstructions in or
near the blower motors. Various shipping materials must be removed
before the blower motor is operated. In addition to the following
start-up and adjustment items, refer to further information in Section
XIII, Operational Checks.
H
A
S
EAT
NTICIPATOR
ETTING
The heat anticipator in the room thermostat must be correctly ad-
justed to obtain the proper number of cycles per hour and to prevent
"overshooting" of the setting. Set the heat anticipator setting to 0.7
amps. Follow the thermostat manufacturer's instructions on how to
adjust the heat anticipator setting.
F
URNACE OPERATION
Purge gas lines of air prior to start-up. Do not purge lines into an
enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
method. Verify that all required kits (propane gas, high altitude, etc.)
have been appropriately installed.
F
S
-
URNACE
TART
UP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by hand.
5. White-Rodgers Models 36E22/36F22/36G22: Push the switch
to the OFF position.
6. Wait five minutes to clear out any gas. Then smell for gas,
including near the floor.
7. If gas can be smelled following the five minute waiting period
in Step 6, immediately follow the instructions on Page 4 of
this manual. If you do not smell gas after five minutes:
White-Rodgers Models 36E22/36F22/36G22: Push the switch
to the ON position.
8. Replace the door on the front of the furnace.
9. Open the manual gas valve external to the furnace.
10. Turn on the electrical power supply to the furnace.
11. Set the room thermostat to the desired temperature.
NOTE: There is an approximate 20 second delay between thermo-
stat energizing and burner firing.
F
JUST
JUST
JUSTMENT
JUST
MENT
MENT
MENT
MENT
URNACE
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the furnace.
3. White-Rodgers Models 36E22/36F22/36G22: Push switch
to the OFF position.
4. Close manual gas shutoff valve external to the furnace.
5. Replace the door on the unit.
G
S
AS
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET
o p e r a t i n g .
GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE
WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.
The line pressure supplied to the gas valve must be within the range
specified below. The supply pressure can be measured at the gas
valve inlet pressure tap or at a hose fitting installed in the gas piping
drip leg. The supply pressure must be measured with the burners
operating. To measure the gas supply pressure, use the following
procedure.
22
S
HUTDOWN
Gas Valve
On/Off
M
Selector
P
Switch
O
F
F
INLET
C
ON
Pressure Regulator
Inlet Pressure Tap
Adjustment
(Side of Valve)
(Under Cap Screw)
Figure 23 - White-Rodgers Model 36E22
Gas Valve
On/Off
Selector
Switch
INLET
Inlet Pressure Tap
Pressure Regulator
(Side of Valve)
Adjustment
(Under Cap Screw)
Figure 24 - White-Rodgers Model 36F22
Outlet Pressure
Tap
INLET
Inlet Pressure
Tap
Figure 25 - White-Rodgers Model 36G22
P
M
UPPLY
RESSURE
EASUREMENT
CAUTION
1
3
2
OUTLET
Outlet (Manifold)
Pressure Tap
(Side of Valve)
OUTLET
Outlet (Manifold)
Pressure Tap
Pressure Regulator
Adjustment
(Under Cap Screw)
OUTLET
Gas Valve
On/Off
Selector
Switch

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

GciGui seriesGci series

Table of Contents