Installing Vent Pipe and Appliance

A. Vent Limits
The abbreviations listed in this vent table key are used in
the vent diagrams.
Description
Minimum Vertical Run Length 13 ft. (4.0 m)
Maximum Vertical Run Length 40 ft. (12 m)
See Figure 8.12 for horizontal venting with optional SLP
venting confi guration.
Vertical terminations are measured to top of chimney.
This appliance is listed for use with LINK-DV systems
and components only. It is permissible to extend venting
above existing chimney (within specifi ed maximum verti-
cal limits) using SLP series or Duravent GS series 4 in. x
6-5/8 in. (101 mm x 168 mm) gas direct-vent pipe. The
link kit will need to be connected to the DV-46DVA-GK to
convert the LINK venting to SLP series. The vent must
be terminated with the cap supplied with the LINK-series
vent kit. Optional colinear to coaxial adapter may be used
to confi gure for SLP series piping. See Section 8.F.
WARNING! Risk of Fire/Explosion/Asphyxiation! Do
NOT connect this gas appliance to a chimney fl ue serving
a separate solid fuel or gas burning appliance.
• May impair safe operation of this appliance or other
appliances connected to the fl ue.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
CAUTION! ALL vent specifi cations MUST be followed.
This product is tested and listed to these specifi cations. Appli-
ance performance will suffer if specifi cations are not followed.
V = 13 FT. (4.0 m) MINIMUM
40 FT. (12 m) MAXIMUM
Figure 8.1
TERMINATION
CAP
ADAPTER
INLET
COLLAR
EXHAUST
COLLAR
EXHAUST
AIR
VENT PIPE
INLET AIR
VENT PIPE
INLET AIR STARTING COLLAR
STARTING COLLAR BRACKET
EXHAUST STARTING COLLAR
Heat & Glo • Supreme-N-I30AU, Supreme-P-I30AU • 2222-900 Rev. E • 6/11
B. Venting Components
CAUTION! Risk of Cuts/Abrasions/Flying Debris.
Wear protective gloves and safety glasses during instal-
lation. Sheet metal edges are sharp.
The vertical vent termination system installed on this model
includes:
• Flexible vent pipe for exhaust air (included with vent kit).
• One length of 3-inch fl exible vent pipe for combustion
air (included with vent kit).
• One pipe-to-cap adaptor (included with vent kit).
• One vertical termination cap (included with vent kit).
C. Connecting Vent Pipe
Reference instructions in the termination kit.
• Install the 3-inch fl exible vent pipe(s) down through the
chimney.
• Secure the exhaust fl exible vent pipe to the exhaust
starting collar on to of the appliance with three screws
and seal with stove cement rated for continuous
exposure to 1200ºF or higher. See Figure 8.1.
• Use 3 screws to attach the section of inlet air vent to
the inlet collar on the collar slide plate and seal with
stove cement rated for continuous exposure to 1200ºF
or higher. See Figure 8.1. NOTE: The collar slide plate
may be removed from appliance to aid installation.
INLET AIR STARTING COLLAR
LOCKING TAB
SEAL WITH STOVE CEMENT
1200º F (649ºC) OR HIGHER
STARTING COLLAR BRACKET
EXHAUST STARTING COLLAR
NOTE: TO ACHIEVE OPTIMUM PERFOR-
MANCE OF INSERT, MINIMIZE OR AVOID
BENDS IN EXHAUST VENT PIPE.
21