Standard Roof Vent (One Elbows No Offsets); Section 3-2-2: Venting Components - Montigo L52DF Installation & Maintenance Manual

L series residential fireplace
Table of Contents

Advertisement

PVTK1
Termination
Figure 9c. Rear vent, Roof mounted venting (1 = 90° bend).

Section 3-2-2: VEnTIng COMPOnEnTS

Select from the following components and associated Montigo part
numbers for installation of a Roof Mounted Termination. Use only
Montigo Vent Components. Use of non-Montigo parts will void the
warranty and may impede operation of the fireplace.
A - Termination
B - Flex Sections
C - Rigid Sections
D - Support Ring &
Plate
E - Firestop
F - Roof Flashing
XG0185 - 050611
Installation
MEXT Sections
Support plate
Support ring
12"
Max.
PVTK-1
PFL - 1
(12" f/f Section)
PFL - 18 (18" f/f Section)
PFL - 2
(24" f/f Section)
PFL - 3
(36" f/f Section)
PFL - 4
(48" f/f Section)
PFL - 6
(72" f/f Section)
PXT - 5
(5" f/f Section)
PXT - 10 (10" f/f Section)
PEXT - 1 (12" f/f Section)
PXT - 20 (20" f/f Section)
PEXT - 2 (24" m/f Section)
PEXT - 3 (36" m/f Section)
PEXT - 4 (48" m/f Section)
PEXT - 6 (72" m/f Section)
PSPXT-8
PS-8
PRF-7
(1/12 - 7/12 pt.)
PRF-12
(7/12 - 12/12 pt.)
Connection and installation of the vent components should adhere to
the following guidelines:
Use any combination of rigid and Flex pipe as required.
Flex sections may be stretched up to 50% of their total length
(e.g. a 24" section maybe stretched to 36").
Connect all vent sections using a minimum of three sheet
metal screws on the outer pipe flue.
Ensure the pipe ends male to female slide in a minimum of
1 1/2" of overlap.
32' max
Ensure all runs are supported with a minimum of 3 supports
per 10' of venting.
When hanging/ supporting venting, ensure that 1" clearance
is maintained on sides and bottom of vent runs and 2" above
horizontal vent runs to any combustible material.
Ensure when cutting sections of rigid pipe to maintain integrity
of internal supports.
Place the springs, supplied with the pipe kit, between the
outer and inner pipes to keep the pipes separate and avoid
any possible hot spots.
Montigo recommends the use of a flex section for the final pipe
connected directly to the fireplace offering greater flexibility of
installation and absorption of movement.
When penetrating a combustible ceiling, a ceiling firestop
must be used.
Montigo recommends that all exterior corners and joints be
sealed with exterior caulking however we encourage you to
consult your Building Envelope Engineer or Waterproofing
Consultant for further recommendations.
L52DF* Indoor Gas Fireplace
Page 9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L52dfnL52dfniL52dflL52dfli

Table of Contents