Safety Features
c)
In cooling mode with compressor energized,
FP2 is less than 40°F [4.5°C] for 30 continuous
seconds.
If a UPS condition occurs, the control will immediately go to
UPS warning. The status LED will remain on as if the control
is in normal mode. Outputs of the control, excluding LED
and alarm relay, will NOT be affected by UPS. The UPS
condition cannot occur during a compressor off cycle. During
UPS warning, the alarm relay will cycle on and off. The cycle
rate will be "on" for 5 seconds, "off" for 25 seconds, "on" for
5 seconds, "off" for 25 seconds, etc.
UPS warning code = 8
Swapped FP1/FP2 thermistors: During test mode, the con-
trol monitors to see if the FP1 and FP2 thermistors are in the
appropriate places. If the control is in test mode, the control
will lockout with code 9 after 30 seconds if:
a)
The compressor is on in the cooling mode and
the FP1 sensor is colder than the FP2 sensor, or:
b)
The compressor is on in the heating mode and
the FP2 sensor is colder than the FP1 sensor.
Swapped FP1/FP2 thermistor code = 9.

CXM Controls

Diagnostic Features
The LED on the CXM board advises the technician of the
current status of the CXM control. The LED can display
either the current CXM mode or the last fault in memory if in
test mode. If there is no fault in memory, the LED will flash
Code 1 (when in test mode).
CXM Control Start-up Operation
The control will not operate until all inputs and safety con-
trols are checked for normal conditions. The compressor will
have a 5 minute anti-short cycle delay at power-up. The first
time after power-up that there is a call for compressor, the
compressor will follow a 5 to 80 second random start delay.
After the random start delay and anti-short cycle delay, the
compressor relay will be energized. On all subsequent com-
pressor calls, the random start delay is omitted.
WATER-TO-WATER (HWW) SERIES
Unit Commissioning & Operating Conditions
Environment – This unit is designed for indoor installation only.
Do not install in an area subject to freezing or where humidity
levels can cause cabinet condensation.
Power Supply – A voltage variation of +/- 10% of nameplate
utilization voltage is acceptable.
Operation and performance is primarily dependent upon water
temperatures, water flow rates and ambient air temperature. This
water to water heat pump is capable of operating over a wide
temperature range and with flow rates of between 1.5 GPM (.1
l/s) and 3 GPM (.19 l/s) per ton, however usually no more than
one of these factors may be at a minimum or maximum level at
a time.
The commissioning table indicates water temperatures which are
suitable for initial unit commissioning in an environment where
the flow rate and water temperature is not yet stable and to avoid
nuisance shut down of the units freeze and refrigerant pressure
safeties.
The operating Table 4 indicates the maximum and minimum
ranges of the unit.
For more specific unit performance reference the product
catalog, the submittal data sheets or contact your supplier for
assistance.
22
Table 4: Building Commissioning
BUILDING COMMISSIONING
Cooling
Unit Size
036
Source Min/Max
50/110
Load Min/Max
60/80
Ambient Min/Max
45/110
BUILDING OPERATING
COOLING
Unit Size
036
Source Min/Max
50/120
Load Min/Max
50/90
Ambient Min/Max
45/110
Installation & Operation
Heating
060/120
036
060/120
50/120
30/80
30/80
60/90
60/120
60/120
39/85
HEATING
060/120
036
060/120
50/120
20/80
20/80
50/90
60/130
60/130
39/85