Technical Data - Potterton Suprima 30 HE Installation & Service Instructions Manual

Condensing central heating boiler
Table of Contents

Advertisement

2. Technical Data

Heat Input - Gross
Heat Output
(Non Condensing)
Heat Output
(Condensing)
Gas Rate
Burner Pressure - Hot
Gas Supply Pressure
Injector Size
Water Content
Boiler Weight
(Lift/Installed - Dry)
Nox Class
Maximum Working Head
Minimum Working Head
Flow Temperature Range
Gas Supply Connection
Flow/Return Connections
Condensate System Connection
Electricity Supply
External Fuse
Internal Fuse
Power Consumption
Electrical Protection
Boiler Type
Boiler Category
Model
Seasonal Efficiency
(SEDBUK) (%)
30
86.1
40
86.4
50
86.2
60
86.2
70
86.2
80
86.2
6
intelligently applied technology
30 HE
kW
10.22
Btu/h
34,877
kW
8.82
Btu/h
30,093
kW
9.50
Btu/h
32,430
3
m
/h
0.98
3
ft
/h
34.5
mbar
8.6
in wg
3.44
mbar
20
mm
2.8
litres
2.3 - 30, 40 & 50
kg
39.0 - 30, 40 & 50
2
SEDBUK Declaration for Suprima HE
This value is used in the UK
Government's Standard Assessment
Procedure (SAP) for energy rating of
dwellings. The test data from which it
has been calculated have been
certified by 0087.
40 HE
50 HE
60 HE
13.62
17.04
20.43
46,465
58,129
69,717
11.78
14.76
17.72
40,181
50,350
60,466
12.64
15.66
18.83
43,111
53,431
64,232
1.30
1.63
1.95
45.9
57.5
68.9
10.4
9.0
8.4
4.16
3.6
3.36
20
20
20
3.1
3.5
3.9
2.7 - 60, 70 & 80
42.8 - 60, 70 & 80
2
2
2
30.5m (100 ft)
150mm (6 in)
63°C - 82°C
15 mm Tail
22 mm Copper
21.5 mm PP
230v ~ 50Hz
3A
Type 3.15AT
80 Watts (excluding pump)
IP20
C
, C
, C
12
32
52
CAT 1
2H - G20 - 20 mbar
2 H
70 HE
80 HE
23.84
27.25
81,343
92,968
20.68
23.63
70,553
80,641
21.89
24.94
74,703
85,105
2.28
2.60
80.4
91.9
11.4
12.8
4.56
5.12
20
20
3.9
4.1
2
2
© Baxi Heating UK Limited 2005

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Suprima 40 heSuprima 50 heSuprima 60 heSuprima 70 he