6.1 Technical specifications

Filter
Tower
Rack
Output Power
@ 230 V
Output Power
@ 208 V
Output Power
@ 200 V
• Rated input voltage
• Input voltage range
• Input frequency
range
• Voltage
• Frequency
• Standard
• Operating
temperature range
• Storage
temperature range
• Relative humidity
• Noise level
(1) The high and low thresholds can be adjusted using UPS settings (up to 150-294 V).
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
620-00082-02-i (en)
Transformer
"AVR"
Charger
5P 650i
5P 650i R
650 VA
420 W
585 VA
378 W
585 VA
378 W
AC Input power
47 to 70 Hz (50 Hz system), 56,5 to 70 Hz (60 Hz system)
Output on battery power
200/208/220/230/240 V (-10/+6 %)
Battery (sealed lead acid, maintenance free)
1 x 12 V
9 Ah
2 x 6 V
9 Ah
Environment
Inverter
Battery
5P 850i
5P 1150i
5P 850i R
5P 1150i R
850 VA
1150 VA
600 W
770 W
765 VA
1035 VA
540 W
693 W
765 VA
1035 VA
540 W
693 W
Single phase 200-240 V
160 to 294 V
(1)
50/60 Hz ±0.1 Hz
Tower
2 x 12 V
2 x 12 V
7 Ah
9 Ah
Rack
4 x 6 V
4 x 6 V
7 Ah
9 Ah
0 to 35 °C
-15 to +50 °C
0 to 90 % (without condensation)
< 40 dBA

6. Appendices

5P 1550i
5P 1550i R
1550 VA
1100 W
1395 VA
990 W
1395 VA
990 W
(2)
(3)
3 x 12 V
9 Ah
6 x 6 V
9 Ah
0 to 40 °C