Temperature Rise; Circulator Blower Speed Adjustment - Amana AMV8 Installation Instructions Manual

Tw-stage gas-fired warm air furnace
Table of Contents

Advertisement

EXAMPLE:
Installation's gas heating (HTG) value: 1,000 BTU/ft
(Obtained from gas supplier)
Installation's seconds per cubic foot: 34 sec/ ft
Conversion Factor (hours to seconds): 3600 sec/hr
Input = (Htg. value x 3600) ÷ seconds per cubic foot
Input = (1,000 BTU/ft
3
Input = 106,000 BTU/hr
This measured input must not be greater than the input
indicated on the unit rating plate.
5. Turn ON gas and relight appliances turned off in step 1.
Ensure all the appliances are functioning properly and that
all pilot burners are operating.
T
R
EMPERATURE
ISE
Air temperature rise is the temperature difference between supply
and return air. The proper amount of temperature rise is usually
obtained when the unit is operated at the rated input with the "as
shipped" blower speed. If the correct amount of temperature rise
is not obtained, it may be necessary to change the blower speed.
An incorrect temperature rise can cause condensing in or
overheating of the heat exchanger. Determine and adjust the
temperature rise as follows. The temperature rise must be within
the range specified on the rating plate or Product Data Book
applicable to your model*.
HEAT EXCHANGER
RADIATION "LINE OF SIGHT"
Temperature Rise Measurement
1. Operate furnace with burners firing approximately 15
minutes. Ensure all registers are open and all duct
dampers are in their final (fully or partially open) position.
2. Place thermometers in the return and supply ducts as
close to the furnace as possible. Thermometers must not
be influenced by radiant heat by being able to "see" the
heat exchanger.
3. Subtract the return air temperature from the supply air
temperature to determine the air temperature rise. Allow
adequate time for thermometer readings to stabilize.
4. Adjust temperature rise by adjusting the circulator blower
speed. Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Refer to the following section for speed changing details.
3
x 3600 sec/hr) ÷ 34 sec/ ft
3
SUPPLY
AIR
T
SUPPLY
T
T
RISE =
-
SUPPLY
RETURN
T
RETURN
RETURN
AIR
C
B
IRCULATOR
LOWER
3
T
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, TURN
OFF
POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS.
All furnaces are shipped with heating speed set at "B" and cooling
speed set at "D". Use the following procedure to select the heating
and cooling speed needed for your unit.
Use the CFM LED (green), adjacent to the integrated control
module fuse to verify airflow quantity. The green CFM LED
blinks once for each 100 CFM of airflow.
1. Determine the tonnage of the cooling system installed with
the furnace. If the cooling capacity is in BTU/hr divide it by
12,000 to convert capacity to TONs.
Example: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system. Most
cooling systems are designed to work with air flows
between 350 and 450 CFM per ton. Most manufacturers
recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer's instructions must be checked
for required air flow. Any electronic air cleaners or other devices
may require specific air flows, consult installation instructions of
those devices for requirements.
3. Knowing the furnace model, locate the high stage cooling
air flow charts in the Product Data Book applicable to your
model* . Look up the cooling air flow determined in step 2
and find the required cooling speed and adjustment
setting.
Example:
A 70 kBtu furnace is to be installed with a 2.5
ton air conditioning system. The air flow
needed is 1000 CFM. Using the cooling
speed chart for the 70 kBtu furnace, find the
airflow closest to 1000 CFM. A cooling airflow
of 990 CFM can be attained by setting the
cooling speed to "C" and the adjustment to "-
" (minus).
NOTE: Continuous Fan Speed will be 56% of
high stage cooling.
4. Locate the blower speed selection DIP switches on the
integrated control module. Select the desired "cooling"
speed tap by positioning switches 1 and 2 appropriately.
Select the desired "adjust" tap by positioning switches 3
and 4 appropriately. Refer to the following figure for switch
positions and their corresponding taps. Turn off power to
furnace for a minimum of 10 seconds, allowing motor to
reset and recognize new speed selection. Turn on power
to furnace. Verify CFM by counting the number of times the
green CFM LED blinks.
5. The multi-speed circulator blower also offers several
custom ON/OFF ramping profiles. These ramping profiles
may be used to enhance cooling performance and increase
comfort level. The ramping profiles are selected using
DIP switches 5 and 6. Refer to the following figure for
switch positions and their corresponding taps. Refer to
the bullet points below for a description of each ramping
profile. Turn off power to furnace for a minimum of 10
seconds, allowing motor to reset and recognize the new
profile selection. Turn on power to the furnace. Verify profile
selection by counting the green CFM LED blinks and timing
each step of the ramping profile.
26
S
A
PEED
DJUSTMENT
WARNING

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Adv8

Table of Contents