Inspection/Installation

Inspection of the New UPS Equipment
Upon receipt of the UPS, a careful inspection for shipping damage
should be made.
After Unpacking:
1) Check the unit for loose, broken, bent or otherwise damaged
parts. If damage has occurred during shipment, keep all original
packing materials for return to shipping agent. Warranty will not
apply to units damaged during shipment.
2) Check to see that the rated capacity and the model number
specified on the nameplate conform to the order specifications.

Installation Precautions

1) Install the unit in a well ventilated location; allow at least 10 cm
(4 inches) on all sides for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position that is free
of vibration.
3) Install the unit where the ambient temperature is between 32°
and 104°F (0° and 40°C).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not install the UPS in a location that will cause direct sunlight
to shine on the unit.
6) Do not install the UPS in areas that are subject to contamination
such as high levels of airborne dust, metal particles, or
flammable gas.
7) Avoid installation near sources of electrical noise. Always make
sure that the unit earth ground is intact to prevent electrical
shock and to help reduce electrical noise.
8) Do not install where water or any foreign object may get inside
the UPS.
9) This UPS generates and can radiate radio-frequency energy
during operation. Although RFI noise filters are installed inside
the unit there is no guarantee that the UPS will not influence
some sensitive devices which are operating close by. If such
interference is experienced, the UPS should be installed farther
away from the affected equipment and/or powered from a
different source than that of the affected equipment.

Operating Precautions

1) The UPS should not be powered up until this entire manual has
been reviewed.