Electrical Phase Conversion
Electrical phase conversion will require a change from single-phase to three-phase or an opposite conversion change
from three-phase to single-phase. Each of these conversions will be explained separately as follows:
Three-Phase to Single-Phase
1. Disconnect blue and yellow wires from terminal L-3 of the terminal block
2. Connect yellow wire to terminal L-1 of the terminal block. The black wires should remain connected to L-1 of the
terminal block as it was originally manufactured.
3. Connect blue wire to terminal L-2 of the terminal block. The red wires should remain connected to L-2 of the
terminal block as it was originally manufactured.
4. Field wiring for the heater power supply will eventually be connected to terminals L-1 and L-2 of the terminal block
when the product is installed.
Single-Phase to Three-Phase
1. Disconnect yellow wire from terminal L-1 of the terminal block
2. Disconnect blue wire from terminal L-2 of the terminal block
3. Connect blue and yellow wires to L-3 of the terminal block
4. Field wiring for the heater power supply will eventually be connected to terminals L-1, L-2, and L-3 of the terminal
block when the product is installed.
Three Phase and Single Phase
Connections at Terminal Block
Terminal Block
Phase
L1
BK & Y
Single
Wires
BK
Three
Wire
6KW
Volt
Conversion Kit
208
265-45246-13
240
265-45246-07
480
265-45246-01
13.5KW
Volt
Conversion Kit
208
265-45246-16
240
265-45246-10
480
265-45246-04
The heaters rating plate will need to be modified because the conversion altered the electrical characteristics of the
heater. This rating plate is placed on every Commercial Electric water heater produced by Bradford White Corporation.
Phase conversion kits above contain rating plate overlays related to the newly created electrical parameters. Follow the
instruction on page 8 For placement of overlays.
L2
L3
R & BL
Wires
R
BL & Y
Wire
Wires
Terminal Block
E32 Series Phase Conversion Rating Plate Overlay Kits
Fuse Block
9KW
Volt
Conversion Kit
208
265-45246-14
240
265-45246-08
480
265-45246-02
15KW
Volt
Conversion Kit
208
265-45246-17
240
265-45246-11
480
265-45246-05
Page 7
FIELD CONVERSION FOR:
KW, Voltage and Phase
12KW
Volt
Conversion Kit
208
265-45246-15
240
265-45246-09
480
265-45246-03
18KW
Volt
Conversion Kit
208
265-45246-18
240
265-45246-12
480
265-45246-06

Hide quick links: