Download Print this page

Hitachi SJ100 Series Quick Reference Manual page 4

Sj100 series
Hide thumbs Also See for SJ100 Series:

Advertisement

Standard
Display
Function
A 01
Frequency Source setting
00-Potentiometer 01-Terminal O/OI
02-Functions F 01 / A 20
A 02
Run command source setting
01-Terminal FW/RV 02-RUN key
A 03
Base frequency setting
A203
Base frequency setting (2. setting)
A 04
Maximum frequency setting
A204
Maximum frequency setting (2. setting)
A 11
External frequency setting start point
A 12
External frequency setting end point
A 13
External frequency setting start point bias (in %)
A 14
External frequency setting end point bias (in %)
A 15
External frequency start pattern setting
00-Per A11 and A13 01-0Hz
A 16
Time constant of the filter for analog inputs
A 20 –
Multispeed frequency setting
A 35
A 38
Jog frequency setting
A 39
Jog stop mode
00-Freerun 01-Deceleration
02-DC brake
A 41
Torque boost selection method
00-Manual 01-Automatic
A241
Torque boost selection method (2. setting)
A 42
Value of manual torque boost setting
A242
Value of manual torque boost setting (2. setting)
A 43
Manual torque boost frequency adjustment (in %)
A243
Manual torque boost frequency adjustment (in %)
(2. setting)
A 44
V/F characteristic setting
00-Constant torque
01-Variable torque
02-SLV
A244
V/F characteristic setting (2. setting)
A 45
V-Gain setting (in %)
A 51
Selection of DC braking operation
00-NO 01- YES
A 52
DC braking frequency setting
A 53
DC braking waiting time setting
A 54
DC braking force setting
A 55
DC braking time setting
A 61
Frequency upper limit setting
A 62
Frequency lower limit setting
A 63,
Jump frequency setting
A 65,
A 67
A 64,
Jump frequency width setting
A 66,
A 68
A 71
Selection of PID control
00-NO 01- YES
A 72
P (proportional) gain setting
A 73
I (integral) gain setting
A 74
D (differential) gain setting
A 75
Scale conversion of PID control setting
A 76
Feedback signal location setting
00-Current 01-Voltage
A 81
Selection of AVR function
00-Available 01-Not available
02-Not available at deceleration
A 82
Selection of voltage of AVR function for the
FE:230/400
motor
FE:230/460
A 92
Second acceleration time setting
A292
Second acceleration time setting (2. setting)
A 93
Second deceleration time setting
A293
Second deceleration time setting (2. setting)
(Table to be continued on next page)
6
(Continued from previous page)
Display
Set
A 94
Selection of method to enable second
Setting
Value
acceleration/deceleration (acc2/dec2)
01
00-Terminal 2CH 01- A 95 / A 96
A294
Selection of method to enable second
acceleration/deceleration (acc2/dec2)
01
(2. setting)
A 95
Changed frequency from acc1 to acc2 setting
50.0
A295
Changed frequency from acc1 to acc2 setting
(2. setting)
50.0
A 96
Changed frequency from dec1 to dec2 setting
A296
Changed frequency from dec1 to dec2 setting
(2. setting)
0
A 97
Pattern of acceleration setting
0
00-Linear 01-S-curve
0
A 98
Pattern of deceleration setting
100
00-Linear 01-S-curve
01
8
All are
Display
0.0Hz
1.0
b 01
Selection of restart mode
00
00-Alarm 01-0.0Hz restart
02-Motor speed match restart
03-Motor speed match restart /decel to stop
b 02
Allowable undervoltage power failure time setting
00
b 03
Retry waiting time
b 12
Level of electronic thermal setting
b212
11
Level of electronic thermal setting (2. setting)
b 13
11
Selection of electronic thermal characteristic
00-Reduced torque 01-Constant torque
10.0
b213
Selection of electronic thermal characteristic
(2. setting)
b 21
Selection of overload limit operation mode
02
00-NO 01-Accel & constant speed
02-Constant speed
b 22
Level of overload limit setting
100
b 23
Rate of deceleration at overload restriction
00
b 31
Selection of software lock mode
00-Terminal, no change
0.5
01-Terminal, frequency change
0.0
02-Keypad, no change
03-Keypad, frequency change
0
b 81
Analog meter adjustment
0.0
b 82
Start frequency adjustment
0.0
b 83
Carrier frequency setting (kHz)
0.0
b 84
Initialization will 00-Clear trip history
0.0
01-Restore data & parameters to factory settings
b 85
Selection of initialized data
b 86
Frequency converted value setting
0.5
b 87
STOP key active in terminal mode
00-YES 01-NO
00
b 88
Selection of operation when FRS signal is
cancelled
1.0
00-Restart at 0 Hz 01-Restart at motor speed
b 89
Selection of contents of remote display
1.0
01-Frequency 02-Current 03-Direction
0.0
04-PID feedback 05-Input terminal status
1.00
06-Output terminal status 07-Scaled frequency
00
b 90
Rate of use (in %) of the regenerative braking
resistor during 100 seconds
02
(00= braking resistor not active)
b 91
Deceleration mode selection when using the
STOP key
00-Deceleration stop
01-Free run stop (FRS)
15.0
b 92
Fan ON/OFF selection
00-Fan is always on
01-Fan is only on if the inverter/motor
15.0
is running
Standard
Set
Function
Setting
Value
00
0.0
0.0
00
00
Standard
Set
Function
Setting
Value
00
1.0
1.0
Rated current
of inverter
01
01
01
Rated current
times 1.25
1.0
01
80
0.5
5.0
00
-FE:01 -FU:02
1.0
00
00
01
00
00
00
7
Standard
Display
Function
Setting
C 01
Function of input terminal 1
00-FW (Forward run) 01-RV (Reverse run)
02-CF1 (Multispeed 1) 03-Multispeed 2
04-Multispd. 3 05-Multispd. 4 06-JG (Jogging)
07-DB (Ext. DC braking) 08-SET (use 2. setting)
09-2CH (2. stage accel/decel) 11-FRS (Free run
mode) 12-EXT (Extern. trip) 13-USP-function
15-SFT (Software lock) 16-AT (Analog input
type) 18-RS (Reset) 19-PTC (only for termi-
nal 5) 27-UP (remote control acceleration)
28-DWN (remote control deceleration)
C 02
Function of input terminal 2 (See C 01 )
C 03
Function of input terminal 3 (See C 01 )
-FE:02 -FU:16
C 04
Function of input terminal 4 (See C 01 )
-FE:03 -FU:13
C 05
Function of input terminal 5 (See C 01 )
-FE:18 -FU:09
C 06
Function of input terminal 6 (See C 01 )
-FE:09 -FU:18
C 11 –
C 14 only
Polarity input of terminal 1-6
00 /
C 16
00-Normally open 01-Normally closed
-FE:00 -FU:01
C 21
Function of output terminal 11
00-RUN-signal 01-FA1 (frequency constant)
02-FA2 (Frequency at set point) 03-OL (Over-
load) 04-OD (PID deviating) 05-AL (Alarm)
C 22
Function of output terminal 12 (See C 21 )
C 23
Function of FM terminal 00-Analog frequency
01-Analog current 02-Digital frequency
C 24
Function of alarm terminal (See C 21 )
C 31
Polarity of terminal 11
00-Normally open 01-Normally closed
C 32
Polarity of terminal 12 (See C 31 )
C 33
Polarity of terminal AL0/AL1
00-Normally open 01-Normally closed
C 41
Level of overload signal setting
Rated current
C 42
Arrival frequency setting for acceleration
C 43
Arrival frequency setting for deceleration
C 44
Level of PID deviation signal setting
C 81
Frequency command adjustment (terminal O)
C 82
Frequency command adjustment (terminal OI)
C 91 –
For further use, do not change.
C 95
Standard
Display
Function
H 01
Autotuning mode:
00-Autotuning off
01-Autotuning on
02-Autotuning/static
H 02
Motor data: 00-Standard Hitachi 01-Auto
H202
Motor data (2. setting)
H 03
Motor capacity
Depending
H203
on model
Motor capacity (2. setting)
H 04
Number of motor poles
H204
Number of motor poles (2. setting)
H 05
Motor constant Kp
H205
Motor constant Kp (2. setting)
H 06
Motor stabilization constant
H206
Motor stabilization constant. (2. setting)
H 20
Motor constant R1
Depending
on model
H220
Motor constant R1 (2. setting)
H 21
Motor constant R2
H221
Motor constant R2 (2. setting)
H 22
Motor constant L
H222
Motor constant L (2. setting)
H 23
Motor constant Io
H223
Motor constant Io (2. setting)
H 24
Motor constant J
H224
Motor constant J (2. setting)
H 30
Motor constant R1 Autotuning
H230
Motor constant R1 Autotuning (2. setting)
H 31
Motor constant R2 Autotuning
H231
Motor constant R2 Autotuning (2. setting)
H 32
Motor constant L Autotuning
H232
Motor constant L Autotuning (2. setting)
H 33
Motor constant Io Autotuning
H233
Motor constant Io Autotuning (2. setting)
H 34
Motor constant J Autotuning
H234
Motor constant J Autotuning (2. setting)
8
Set
Value
00
01
:
01
00
00
05
01
01
01
0.0
0.0
3.0
-
-
Set
Setting
Value
00
00
4
20
100
These
para-
meters
must not
be
changed!

Advertisement

loading

This manual is also suitable for: