Quadra-Fire QV32B-A Owner's Manual page 27

Installation and operation
Hide thumbs Also See for QV32B-A:
Table of Contents

Advertisement

Top Vent - Vertical Termination
No Elbow
Note: Use SLP Series
components only.
Note: If installing a vertical vent/termination off the top of
the appliance, the optional vertical termination baffl e may be
needed.
V
= 60 ft. Max. (18.3 m)
1
Figure 7.7
Exhaust restrictors are recommended for these verti-
cally terminated products which have excessive draft.
Exhaust restrictors will compensate for high draft, and
restore visual fl ame height. If the vent confi guration has
a total vertical of 15-60 feet, an exhaust restrictor may
be needed. The exhaust restrictor can be located in the
appliance manual bag.
V
1
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. U • 1/12
Exhaust restrictor Instructions
1. Install the exhaust restrictor over the center of the ex-
haust outlet in the fi rebox (see Figure 7.8).
2. Center the exhaust restrictor in the open end of the
exhaust outlet and secure through the slots on the ex-
haust restrictor with the 2-1/4 in. self tapping screws
provided in the appliance manual bag.
INNER HEAT SHIELD
To access the
exhaust openings,
remove the inner
heat shield. To
remove inner heat
shield, remove the
two screws.
Top Vent Application
Exhaust restrictor
Rear Vent Application
Exhaust restrictor
Note: Be sure to re-
install the inner heat
shield after exhaust
restrictor installation.
Figure 7.8
27