Toshiba MMK-AP0071H Installation Manual page 9

Super modular multi system air conditioner
Hide thumbs Also See for MMK-AP0071H:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 4
• To increase effect of drain, confirm the unit is
installed horizontally or slightly lowering rightward
viewed from the front side.
Lowering rightward viewed
from the front side
Horizontal installation
• Do not install the unit by plugging in the wall.
Indoor unit
Installation of installation plate
• Using the installation pattern, determine the installation position of the indoor unit, and drill the pipe hole matching
with the position indicated in the installation pattern. When passing the refrigerant pipe through wall using metal
mesh, be sure to use insulation sleeve such as polyvinyl chloride pipe.
In case of wooden construction (Wide wall)
(1) Determine vertical position of the installation plate by interval (height) between the indoor unit and the ceiling.
(2) Determine the position so that screw hole of installation plate locates at the center of pillar or stud by adjusting
left/right position without changing height of the installation plate.
(3) Tighten the screws (accessory parts) after bore preholes with a gimlet in the stud to prevent the crack.
In case of reinforced concrete construction
(1) After drilling holes with interval by 150mm at the selected
positions on the concrete wall, strike in grip anchor or
hole-in anchor.
(2) Fix the installation plate to the anchor with bolt or nut.
However, when using hole-in anchor, adjust drilling depth
so that screw head-out is 10mm or less.
• Conduit tube may be buried in the concrete wall. Ask the constructor it.
• Before installation of the indoor unit, be sure to check whether the installation plate has been completely
installed.
In case of rear direction piping
Using the installation pattern, determine the pipe hole position, and drill a pipe hole slightly lowering downward.
Lowering leftward viewed
from the front side
REQUIREMENT
• The mass including installation plate of the indoor
unit is shown in the following table. Check whether
the wall has sufficient intensity.
Model MMK-
0071H to 0121H
0151H to 0181H
0241H
• When installing the side plate, check the status that
hook is inserted in square hole. Push in the side
plate until it is stuck closely to the indoor unit.
Hook
Grip anchor
Bolt
Installation plate
6
Mass (kg)
20
22
29
Square hole
Screw cap
Side plate fixing screws
Hole-in anchor
Nut
screw
dia. Ø8
Installation
plate
10mm
Concrete
or less
wall
Concrete
wall

Advertisement

Table of Contents
loading

Table of Contents