fIgURE 14 – Steam Humidifier wiring and Utility Diagram
INPUT POwER
with ground.
Refer to wiring
STEAM
diagram .
OUTlET
Aprilaire Model 1150/1160/1180
Steam Humidifier
DRAIN wATER OUT
¾" COPPER or 1" HOSE
Field Wiring Terminal Block Designations
Command Signal
Normally Closed, Common, &
1
NC
Normally Open relay terminals
2
Enable Input
O
for optional blower control by
+24 VDC
30
NO
humidifier or remote fault alarm
20
1
2 30 NC O NO C
fIElD
?????
????
?????
??????
wIRINg
Steam Fill Drain On/Off
TERMINAl
blOCK
SUPPly wATER IN
¼" COMPRESSION FITTING
High Voltage Wiring
Low Voltage Wiring
1+ 1- 24V C H+ H- ODT
2 wire shielded
cable with
ground shield
connected to C
3 wire shielded cable
with ground shield
connected to C
C
NO
NC
Automatic Steam
Humidifier Control
Terminal Designations
1+, 1- Serial Communications
(for optional devices)
H+
Command Signal to
Humidifier
H-
Command Signal to
Ground (not used)
To Outdoor
Temperature
Sensor
Airflow Proving
C
Switch
NO
Connect ¼" plastic
NC
tubing from H (High)
side of proving switch
to the airflow sensing
probe located 1 .5 duct
diameters downstream
of blower . Leave L
(Low) side open to
atmosphere .
High Humidity
limit Switch
Switch will be closed
below high limit set
point
90-928