1. Sudden operation may cause personal injury or property damage on Models 220, 22x4, 440, 550A, 550, 560A and 560 humidifiers. Turn Auto-Trac™ Control 220, 224, 400, 440, 550, 550A, 558, 560, 560A, 568 and 600 humidifiers. Turn System of manual humidistat to “Off” or lowest setting before servicing or the Humidifier Control or manual humidistat to “Off”...
Page 4
4,200 3,000 *Based on 8' ceiling height. Models 220, 224, 400, 440, 445, 445A, 448, 550, 550A, 558, 560, 560A, 568 and 600 Total Static Pressure Drop Across Supply & Return Plenum ………………………………0.2" (1) Calculations are based on: (2) Calculations are based on: a.
A drain safety overflow has been molded into the lower housing of all the black plastic Aprilaire units. This safety overflow is designed to eliminate water inside of the furnace plenum if there is a malfunction. Removing dips and hills from the drain line and flushing it with water under pressure will eliminate the problem.
Page 6
The design feed rate is 3 gph for the Models 110, 220, 550, 550A, 558, 560, 560A, 568 and 600. This feed rate will fill a quart jar in 5 minutes. The design feed rate for the Models 112, 224, 330, 350, 360, 440, 760, 760A, 768 and 700 is 6 gph.
INDIVIDUAL UNIT SERVICE—MODELS 220-224-400-440-550-550A-558-560-560A-568-600 CAUTION: 1. Sudden operation may cause personal injury or property damage. Turn the Automatic Humidifier Control or manual humidistat to "Off" or lowest setting before servicing or troubleshooting these units. I. LACK OF HUMIDITY ● Check The Home — See Pages 2 and 3.
Page 8
III. LEAKING WATER — See Page 4. The Models 220 and 224 are provided with a cover over the distribution tray. These covers are quite effective in minimizing water bubbling out of the feed tray up to approximately 0.4 in. static pressure. A damper should be included in the bypass between the supply and return plenum to relieve the pressure that can be created by zone dampers completely closed with the furnace blower still operating.
Page 9
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODELS 220 & 224) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 8 -...
Page 10
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODEL 440) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 9 -...
Page 11
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODELS 550, 550A, 558 / 560, 560A, 568) 15A or 15B Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 10 -...
Page 12
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODEL 400) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 11 -...
Page 13
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODEL 600) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 12 -...
Page 14
The fan blade should be tight on the shaft and 1/3 through the orifice plate toward the motorboard. If not, reposition the fan and tighten set screw to flat on the motor shaft. Aprilaire Humidifier Control Manual Humidistat APRILAIRE HUMIDIFIER...
Page 15
The motor will operate if power is connected to the unit, the furnace blower is running and the humidistat switch is closed. To check the fan motor: APRILAIRE HUMIDIFIER CONTROL- AUTOMATIC AND MANUAL MODE 1. Replace the cover assembly and reconnect power.
Page 16
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODELS 760 760A 768 & 700) or 1B Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 15 -...
Page 17
INDIVIDUAL UNIT SERVICE—MODELS 445, 445A & 448 WARNING: 1. 120 VOLTS may cause serious injury from electrical shock. Disconnect power and shut off water supply before servicing or troubleshooting this unit. 2. Rotating or electrical components may cause serious injury from con- tact.
Page 18
The Model 445, 445A and 448 are circulating units which will require maintenance every 30 days. Complete servicing instructions for both the water reser- voir and circulating pump are located in the homeowners manual. Aprilaire Humidifier Control Manual Humidistat NOTE...
Page 19
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODELS 445, 445A & 448) 20A or 20B Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 18 -...
INDIVIDUAL UNIT SERVICE—MODELS 350 & 360 WARNING: 1. 120 VOLTS may cause serious injury from electrical shock. Disconnect power and shut off water supply before servicing or troubleshooting these units. 2. Rotating or electrical components may cause serious injury from con- tact.
Page 21
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODEL 350) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 20 -...
Page 22
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODEL 360) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. - 21 -...
If either the motor or solenoid valve is not operating and the other is operating, the relay trans- former and humidistat can be eliminated as a source of trouble. Disconnect electrical power and replace the motor or solenoid valve whichever is not working. APRILAIRE HUMIDIFIER GREEN GROUND...
Page 24
SORY TERMINALS THAT CAN BE USED FOR THE HUMIDIFIER. THE RP MODEL 50 RELAY MAY NOT BE NECESSARY IN THIS CASE. CONSULT THE FURNACE MANFACTURER'S RECOMMENDATIONS FOR WIRING. HUMIDISTAT CURRENT SENSING RELAY 110 & 112 APRILAIRE HUMIDIFIER BLACK BRACKET COMMON YELLOW LEAD WATER BLACK...
Page 25
EXPLODED RP APRILAIRE PLENUM HUMIDIFIER (MODELS 110 & 112) Instructions for Ordering Parts Specify: MODEL NO. — PART NAME — PART NO. -24 -...
Page 26