Vitodens 100-W, WB1B Installation & Service
Installation Examples
Vitodens 100-W, WB1B 10-26, 10-35 with...
-
CombiPLUS Kit
-
low-loss header
-
one heating circuit
Legend
AV
Air vent
PRV Pressure relief valve (boiler)
PRV* Pressure relief valve (DHW 150 psi)
WSE Water softner equipment
A
Vitodens 100-W gas-fired condensing boiler
B
External boiler / system controller (field supplied)
C
Heating circuit
D
Heating circuit pump (field supplied)
E
CombiPLUS
F
LLH
G
Expansion tank
(continued)
Note: The use of a low-loss header is recommended if the
water flow rate is less than 1.7 GPM (400 L/h) or
more than 6.2 GPM (1400 L/h).
The low-loss header is available as accessory part.
Maximum Flow Rates
Model WB1B
∆ t
Output Btu/h
30° F rise (GPM)
35° F rise (GPM)
40° F rise (GPM)
Connections
26
35
83,000
108,000
5.5
---
4.7
6.2
4.2
5.4