Viessmann Vitodens 100-W WB1B Series Installation And Service Instructions Manual page 39

Vitodens 100-w wb1b series wall-mounted, gas-fired condensing boiler with optional on demand hot water combiplus kit
Table of Contents

Advertisement

Vitodens 100-W, WB1B Installation & Service
Installation Examples
System Layout 2
Vitodens 100-W, WB1B 26, 35 with...
- DHW storage tank
- low-loss header
- one heating circuit
AV
PRV
IMPORTANT
Primary pump L must pump into the boiler (as illustrated).
Note: The use of a low-loss header is recommended if the
water flow rate is less than 1.7 GPM (400 L/h) or
more than 6.2 GPM (1400 L/h).
The low-loss header is available as an accessory part.
See page 49 in this manual for details on the low-
loss header.
(continued)
TPV
Legend
AV
Air vent
PRV Pressure relief valve
TPV Temperature and pressure relief valve
A
Vitodens 100-W gas-fired condensing boiler
B
External boiler/DHW controller (field supplied)
C
Heating circuit
D
Heating circuit pump (field supplied)
E
DHW storage tank
F
DHW tank temperature aquastat or sensor
G
DHW circulating pump field supplied)
H
Low-loss header
K
Expansion tank
L
Primary pump (boiler circuit, field supplied) with
low-loss header only
Maximum Flow Rates
Model
WB1B
∆ t
Output Btu/h
30º F rise (GPM)
35º F rise (GPM)
40º F rise (GPM)
Connections
26
35
83,000
108,000
5.5
----
4.7
6.2
4.2
5.4
39