generator output voltages
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the voltage selector switch (Figure 15). To obtain some of
the voltages as listed in Table 9 (see below) will require a
fine adjustment using the voltage regulator (VR) control
knob located on the control panel.
voltage selector switch
The voltage selector switch (Figure 15) is located above
the output terminal panel's Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection..
Figure 15. Voltage Selector Switch
caution
never change the position of the voltage selector
switch while the engine is running. alWaYs place
circuit breaker in the OFF position before selecting
voltage.
table 9. voltages available
uvWo output
voltage selector switch
terminal lugs
3-phase 240/139v position
208V
3Ø line-line
1Ø line-neutral
120V
voltage selector switch single-phase 240/120v position
1Ø line-neutral/
120V
Line-Neutral
line-line
dca70SSJU4i 60 hz generator• operation manual — rev. #2 (04/09/14) — page 27
voltage selector switch
3-phase 480/270v position
220V
240V
416V
440V
127V
139V
240V
254V
240V
N/A
N/A
N/A
Line-Line

GeNeratOr OUtpUts

maximum amps
Table 10 shows the maximum amps the generator can
provide. dO NOT exceed the maximum amps as listed.
table 10. generator maximum amps
rated voltage
1Ø 120 Volt
1Ø 240 Volt
3Ø 240 Volt
3Ø 480 Volt
gFci receptacle load capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the three twist lock auxiliary receptacles.
Figure 18 and Table 12 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
table 11. 1Ø gFci receptacle load capacity
twist lock (c6369)
480V
table 12. 3Ø generator maximum amps
277V
(uvWo terminals)
N/A
maximum amps
155.5 X 2 amps (4 wire)
168 amps X 2 (Zigzag)
78.8 amps (4 wire)
168 amps (Zigzag)
168 amps
84 amps
KW in Use
available load
current (amps)
GFCI Duplex
1Ø 240/120V
5-20R 120V
40.4
0
39.2
5 amps/receptacle
38.0
10 amps/receptacle
38.6
15 amps/receptacle
35.6
20 amps/receptacle
Kva in use
available load
current (amps)
GFCI Duplex
3Ø 240/480V
5-20R 120V
70
0 amps/receptacle
65.8
5 amps/receptacle
61.7
10 amps/receptacle
57.5
15 amps/receptacle
53.4
20 amps/receptacle