Engine/Generator Control Panel - MULTIQUIP Whisperwatt DCA70SSJU4i Operation And Parts Manual

Whisperwatt series 60hz generator (john deere 4045hfg92 diesel engine)
Table of Contents

Advertisement

50
25
75
PSI
0
OIL PRESS
The definitions below describe the controls and functions
of the Engine/Generator Control Panel (Figure 7).
1. gauge Unit assembly — This assembly houses the
various engine monitoring gauges. These gauges
indicate: oil pressure, water temperature, charging
voltmeter, fuel and engine speed RPM (tachometer).
A. Oil pressure gauge — During normal operation
this gauge be should read between 35 to 65 psi.
(241~448 kPa). When starting the generator the
oil pressure may read a little higher, but after the
engine warms up the oil pressure should return to
the correct pressure range.
B. Water Temperature gauge — During normal
operation this gauge be should read between 185°
and 207°F (85°~97°C).
C. charging voltmeter gauge — During normal
operation this gauge indicate minimum 14 VDC
D. Fuel gauge — Indicates amount of diesel fuel
available.
E. Tachometer — Indicates engine speed in RPM's
for 60 Hz operation. This meter should indicate
1800 RPM's when the rated load is applied.
2. Fuel leak detected alarm lamp — This lamp when
ON indicates that fluids in the containment area have
reach a high level.
3. panel light switch — When activated will turn on
control panel light.
4. panel light — For operation at night, panel light
illuminates control panel for ease of reading meters
and gauges. Make sure panel light switch is in the OFF
position when light is not in use.
page 22 — dca70SSJU4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14)

eNGiNe/GeNeratOr CONtrOL paNeL

1
A
B
C
180
18
140
12
220
24
°F
VOLTS
100
100
260
6
30
WATER TEMP
BATTERY
D
E
½
150
120
180
60
°F
RPMX10
E
0
F
210
FUEL
SPEED
Figure 7. Engine/Generator Control Panel
4
2
3
5
50
180
18
25
75
140
220
12
24
PSI
°F
VOLTS
0
100
100
260
6
30
OIL PRESS
WATER TEMP
BATTERY
½
150
120
180
60
RPMX10
E
0
F
210
FUEL
SPEED
6
ECU
Series 800 Controller
Engine Started
7
Shutdown
Pre-Alarm
Alarm
Screen
Program
Option
Acknowledge
Change
Exit
12
13
5. Frequency meter — Indicates the output frequency
in hertz (Hz). Normally 60 Hz
6. ac ammeter — Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.
7. ac voltmeter — Indicates the output voltage present
at the u,v, and W output terminal lugs.
8. voltage regulator control — Allows ±15% manual
adjustment of the generator's output voltage.
9. ammeter change-over switch — This switch allows
the AC ammeter to indicate the current flowing to the load
connected to any phase of the output terminals, or to be
switched off. This switch does not effect the generator
output in any fashion, it is for current reading only.
10. voltmeter change-over switch — This switch allows
the AC voltmeter to indicate phase to phase voltage
between any two phases of the output terminals or to
be switched off.
11. main circuit Breaker — This three-pole, 200 amp
main breaker is provided to protect the u,v, and W
output terminal lugs from overload.
12. auto/start switch — This switch selects either manual
or automatic operation . Center position is OFF (reset).
13. hour check Button — With the engine stopped, press
and hold this button. The total running hours, fuel level,
and battery voltage will be displayed.
8
INCREASE
DECREASE
11
V
9
U
W
OFF
V-W
10
U-V
W-U
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents