Honeywell FocusPRO TH6220D Installation Manual page 14

Honeywell programmable thermostat installation guide
Hide thumbs Also See for FocusPRO TH6220D:
Table of Contents

Advertisement

Installation Guide
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
To begin, press and hold the
buttons until the display changes
Setup Function
8
Emergency heat
cycle rate (CPH)
9
Compressor
cycle rate (CPH)
10
Second stage
compressor cycle
rate (CPH)
12
System setting
adjustment
13
Adaptive Intelli-
gent Recovery
14
Temperature
display
15
Compressor
protection
16
Schedule format
27
Heat temperature
range stops
28
Cool temperature
range stops
and
F F A A N N
Settings & Options
9 For electric emergency heat
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
5 For gas or oil furnaces of less than 90% efficiency
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/Cool/Auto/Off)
2 Auto changeover only (Auto)
1 On
**See page 14
0 Off
0 Fahrenheit
1 Celsius
5 Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
0 5/2 (programmable weekdays and weekends)
1 5/1/1 (weekdays, Saturday & Sunday programmable)
90
Highest heating temperature setting
40-89 Heating temperature range (increments of 1°F, or 0.5°C)
50
Lowest cooling temperature setting
51-99 Cooling temperature range (increments of 1°F, or 0.5°C)
Function
number
1
Done
Press
Press
N N E E X X T T
Press
D D O O N N E E
**See page 14
12
Setting
Next
or
to change settings
to advance to next function
to exit and save settings
**See page 14
**See page 14
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents