Figure 16 Di Module Terminal Block Connections - Honeywell UMC800 Installation And User Manual

Honeywell umc800 controller installation and user guide
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Module B
Identifiable by
32 screws
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Module ID B (16 DI)
Logic Input (Contact Closure)
For 2 wires per DI, must use 22-gage wire to fit 32
wires through rubber grommet on case.
Field Wiring
Dry SW
Module ID B (16 DI)
Logic Input (Contact Closure)
For 1 common wire for all DIs, use 16-22 gage wire.
Field Wiring
Dry SW
Release F
4/01
Each odd-numbered
terminal is internally
grounded.
+
Gnd
DI 16
DI 15
DI 14
DI 13
DI 12
DI 11
DI 10
DI 9
DI 8
DI 7
DI 6
DI 5
DI 4
DI 3
DI 2
DI 1
R
Gnd
+ VCC
R
Gnd
+ VCC
• One wire per DI. Each wire goes to
Marshalling field connector (user provided).
• One common wire from Marshalling field
connector to any ground connector on the
16 pt. DI terminal.
Marshalling field
connector

Figure 16 DI module terminal block connections

UMC800 Controller Installation and User Guide
12
Module ID
#3, 4, or 5
11
10
9
8
7
6
5
4
3
2
1
Module ID #3
Logic Input (Contact Closure)
Field Wiring
Logic
Module ID #4
DC Input (24 Vdc)
Field Wiring
+
24V
-
Logic
Module ID #5
AC Input (120/240 Vdc)
Field Wiring
Dry SW
L1
L2
Mounting and Wiring
Signal Wiring
DI 6
DI 5
DI 4
DI 3
DI 2
DI 1
R
Gnd
+ VCC
+ VCC
+
R
-
+ VCC
R
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents