Stuck Gas Valve Alarm; Network Accessible Variables - Carrier 33CS Installation, Service, And Troubleshooting Instructions

Temp system unitary controller thermostat
Table of Contents

Advertisement

When the CO
level exceeds the preset level (factory con-
2
figuration is 1000 ppm and cannot be changed without optional
software), the sensor signals the TEMP system thermostat. The
TEMP system thermostat energizes the indoor-fan motor (if
not already running) for 5 to 30 minutes (field-configured). If
the Auxiliary Relay has been configured for IAQ operation, the
TEMP system thermostat energizes the relay. This is intended
for use with an economizer, but can be wired to an exhaust fan
or HRV (Heat Recovery Ventilator). If used with an economiz-
er, the economizer moves to the minimum position and the in-
door fan circulates the air throughout the occupied space.
The TEMP system has 3 lockout features which will pre-
vent IAQ mode if the outdoor humidity is too high or the out-
door temperature is too high or too low. When the TEMP sys-
tem thermostat energizes the auxiliary relay, it energizes the
system fan.
At the end of the 5 to 30 minutes, if the CO
ceeds the set point, the indoor fan will stay energized. The
economizer damper opens. This forces fresh outside air to enter
the zone with deficient IAQ. When the IAQ level drops below
the IAQ set point, the economizer returns to its standard operat-
ing mode.
When the system is bringing in additional outside air, the
thermostat is reset 0 to 10° F (field-configured) above and be-
low the original set point to allow the outside air to circulate
before the heating or cooling mode is initiated. The TEMP sys-
tem thermostat will display status when the system is in this
mode.
CLEARING THE ALARM — To clear a system error, use the
Unit Reset function. The Unit Reset function is in category 7,
option 11. The default is OFF. Use the left set point buttons to
set the option to ON. The TEMP system thermostat will reset
all errors.
Stuck Gas Valve Alarm —
Gas Valve alarm specifications.
Table 11 — Stuck Gas Valve Alarm
FUNCTION
Controllers
Sensor Required
Sensor Wiring
Input
Output
Category/Option
Configuration Values
Configuration Increments
Associated Functions
OPERATION — The Stuck Gas Valve sequence is used to
allow the system to properly react to a failure mode of the
HVAC unit when the gas valve becomes stuck in the open
position. When this condition exists, the unit is unable to shut
off the heat. To minimize this problem, the internal limit switch
trips causing the indoor fan to turn on and remain on until the
gas is manually shut off and the heat exchanger cools to nor-
mal temperatures.
During No System Mode — If the duct temperature rises to
greater than 175 F, the indoor fan is started. The fan will remain
on if that temperature does not drop below 150 F after 3 min-
utes. A Stuck Gas Valve alarm (SE13) will be initiated.
level still ex-
2
Refer to Table 11 for Stuck
DESCRIPTION
TEMP System Thermostat
N/A
N/A
Duct Temperature Sensor
SE13, Stuck Gas Valve Alarm
None
None
None
None
During a Cooling Mode — If the duct temperature does not
drop below 80 F within 10 minutes, the cooling mode will be
dropped for 10 minutes. The ''No System Mode'' logic will
test for this condition.
During a Heating Mode — No action is required in this mode.
CONFIGURATION TO ACTIVATE ALARM — No configu-
ration is needed to activate this alarm.
CONFIGURATION TO NORMALIZE ALARM — To
remove this alarm, follow the procedure to clear the alarm
from the thermostat and network using manual reset.
CLEARING THE ALARM FROM THE THERMOSTAT —
The alarm can be cleared or erased from the system in 2 ways:
• Cycle power to the thermostat off, then on.
• Initiate a reset by switching the Unit Reset option to the ON
configuration (category 7, option 11).

NETWORK ACCESSIBLE VARIABLES

When using network access software, the following tables
can be accessed. The variables in the tables can be read, writ-
ten, or forced to a certain value. The TEMP system thermostat
point display table is shown in Table 12. Other network soft-
ware access tables are shown in Table 13.
Table 12 — TEMP System Thermostat Point
Display Table
VARIABLE
DESCRIPTION
Zone Temperature
Duct Temperature
Outside-Air Temperature
Zone Demand
Demand Type
Controller Set Point
Occupied
System Cool Stage 1
System Cool Stage 2
System Heat Stage 1
System Heat Stage 2
System Fan
Auxiliary Relay
System Fan Status
DX Coil Temperature
Filter Status
TEMP IAQ Sensor
Zone In IAQ Status
Indoor Rel. Humidity
Outdoor Rel. Humidity
HVAC Usage Meter (Mtr)
Override (Ovrd)
Usage Mtr
HVAC Ovrd Usage Mtr
LEGEND
DX — Direct Expansion
IAQ — Indoor-Air Quality
*Forcing the system fan will cause any energized system stages to
turn off.
†If Auxiliary Relay is configured as 0 or 1, the point can be forced
with no other effect. Other configurations will cause the system
stages and fan to turn off.
29
READ/WRITE
POINT NAME
CAPABILITY
ZT
YES
DT
YES
OAT
YES
ZDMD
READ ONLY
DMDTYPE
READ ONLY
SETPOINT
READ ONLY
OCC
YES
C1
READ ONLY
C2
READ ONLY
H1
READ ONLY
H2
READ ONLY
FN
YES*
AUX
YES†
FANS
YES
DX
YES
FILS
YES
IAQLOG
YES
ZONEIAQ
READ ONLY
RH
YES
OARH
READ ONLY
UMHVAC
YES
UMUO
YES
UMUOSM
YES

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents