Global Schedule Broadcast; Daylight Savings Time; Holiday Schedules - Carrier 33CS Installation, Service, And Troubleshooting Instructions

Temp system unitary controller thermostat
Table of Contents

Advertisement

To set the option, configure category 9, option 1. Use the
left set point buttons to toggle the option ON or OFF. The de-
fault is OFF.
NOTE: Broadcast Acknowledgement works best when config-
ured in a Zone Controller, TEMP system thermostat, or any
other CCN device which can be configured as a broad-
cast acknowledger. Avoid using a monitor thermostat when
possible.
Global Schedule Broadcast —
Schedule Broadcast is set to ON, the TEMP system thermostat
will broadcast its occupancy schedule to the CCN (network).
The schedule number will be used to define the number of the
occupancy table broadcasted. Global schedules are occupancy
schedules 65 to 99.
NOTE: Unoccupied Override will not work if the TEMP sys-
tem thermostat is following a global schedule.
When the Global Schedule Broadcast is set to OFF, the
TEMP system thermostat will not broadcast its occupancy
schedule.
To set the option, configure category 9, option 2. Use the
left set point buttons to toggle the option ON or OFF. The de-
fault is OFF.
NOTE: If using Global Schedule Broadcast, then Schedule
Number (category 2, option 9) must be set to a value between
65 and 99.
Daylight Savings Time —
stat supports daylight savings time. The start date and stop
dates are entered by the user and the time is automatically ad-
justed forward and backward at the configured times. The
modified date and time is sent to other network devices if
the TEMP system thermostat is a Network Time Broadcast
Device.
Only the time broadcaster can do a daylight savings broad-
cast. If other TEMP system thermostats are on the network,
and they are configured not to receive network time, these
TEMP system thermostats will not support daylight savings
time functions.
DAYLIGHT SAVINGS TIME START MONTH — The Day-
light Savings Time Start Month tells the TEMP system ther-
mostat which month to move its internal clock forward for
daylight savings time. To set the month, configure category 9,
option 6. Use the left set point buttons to raise or lower the
value. January is 1, February is 2, and so on. The range of val-
ues is 1 to 12. The default is 4.
DAYLIGHT SAVINGS TIME START WEEK — The Day-
light Savings Time Start Week tells the TEMP system thermo-
stat which week to move its internal clock forward for daylight
savings time. To set the week, configure category 9, option 7.
Use the left set point buttons to raise or lower the value. The
first week of the month is 1, the second week of the month is 2,
and so on. The last week of the month (in 4 or 5 week months)
is always 5. The range of values is 1 to 5. The default is 1.
DAYLIGHT SAVINGS TIME START DAY — The Daylight
Savings Time Start Day tells the TEMP system thermostat
which day to move its internal clock forward for daylight sav-
ings time. To set the day, configure category 9, option 8. Use
the left set point buttons to raise or lower the value. The first
day of the week is 1 (Monday), the second day of the week is 2
(Tuesday), and so on. The range of values is 1 to 7. The default
is 7 (Sunday).
DAYLIGHT SAVINGS TIME MINUTES TO ADD — The
Daylight Savings Time Minutes To Add option tells the TEMP
system thermostat how many minutes to move the clock for-
ward for daylight savings time. To set the number of minutes,
configure category 9, option 9. Use the left set point buttons to
When the Global
The TEMP system thermo-
raise or lower the value. The range of values is 0 to 90 minutes.
The default is 60 minutes.
DAYLIGHT SAVINGS TIME STOP MONTH — The Day-
light Savings Time Stop Month tells the TEMP system ther-
mostat which month to move its internal clock back for the end
of daylight savings time. To set the month, configure category
9, option 10. Use the left set point buttons to raise or lower the
value. January is 1, February is 2, and so on. The range of val-
ues is 1 to 12. The default is 10.
DAYLIGHT SAVINGS TIME STOP WEEK — The Daylight
Savings Time Stop Week tells the TEMP system thermostat
which week to move its internal clock back for the end of day-
light savings time. To set the week, configure category 9,
option 11. Use the left set point buttons to raise or lower the
value. The first week of the month is 1, the second week of the
month is 2, and so on. The last week of the month (in 4 or 5
week months) is always 5. The range of values is 1 to 5. The
default is 5.
DAYLIGHT SAVINGS TIME STOP DAY — The Daylight
Savings Time Stop Day tells the TEMP system thermostat
which day to move its internal clock back for the end of day-
light savings time. To set the day, configure category 9, option
12. Use the left set point buttons to raise or lower the value.
The first day of the week is 1 (Monday), the second day of the
week is 2 (Tuesday), and so on. The range of values is 1 to 7.
The default is 7 (Sunday).
DAYLIGHT SAVINGS TIME MINUTES TO SUBTRACT
— The Daylight Savings Time Minutes To Subtract option tell
the TEMP system thermostat how many minutes to move the
clock back at the end of daylight savings time. To set the num-
ber of minutes, configure category 9, option 13. Use the left set
point buttons to raise or lower the value. The range of values is
0 to 90 minutes. The default is 60 minutes.

HOLIDAY SCHEDULES

The TEMP system thermostat supports holiday scheduling.
Eighteen different holidays can be user-defined. Each holiday
has a start date (month and day) and a duration. When a user-
defined holiday occurs, the TEMP system thermostat follows
the holiday schedule defined in the occupancy periods.
To define a holiday, toggle to category 10. Each option (hol-
iday schedule) has 2 screens. The first option screen shows the
month and day. The second option screen shows the duration.
The default values are 0 for each schedule. Press the enter but-
ton on the first screen to modify the month and day. The month
will flash. Use the left set point buttons to scroll through the
months. January is 1. February is 2, and so on. The range of ac-
ceptable values is 0 to 12. Set the month to 0 to disable the hol-
iday schedule.
Once the month has been selected, press the enter button.
The day will flash. Use the left set point buttons to scroll
through the days. The range of acceptable values is 0 to 31. Set
the day to 0 to disable the holiday schedule. Press enter again to
return to the option selection screen. Toggle to the second
screen of option 10.1 by pressing the upper left set point button.
Press the enter button. The duration will flash. The duration is
the number of days the holiday schedule will be active. The
range of acceptable values is 0 to 99. Set the value to 0 to dis-
able the holiday schedule.
Options 10.1 through 10.18 are configured in the same
manner.
NOTE: If the network time broadcaster has a configured holi-
day schedule, it will broadcast that the day is a holiday for
other CCN devices. The Comfort System thermostats will
ignore this information. In order to broadcast a global holiday,
a global schedule broadcast must be used (schedules 65 to 99).