CGs-4E Gas-Fired Water Boiler — Boiler Manual
GOLD
1c
Prepare boiler location — vent system
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe
personal injury or death.
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause
severe personal injury or death.
DO NOT COMMON VENT
cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death or substantial
property damage.
When removing boiler from an
existing common vent system:
At the time of removal of an existing boiler, the fol-
lowing steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remain-
ing connected to the common venting system are not
in operation.
Seal any unused openings
a.
system.
Visually inspect the venting system
b.
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion or other
deficiencies which could cause an unsafe condi-
tion.
Test vent system
c.
building doors and windows and all doors between
the space in which the appliances remaining con-
nected to the common venting system are located
and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the com-
mon venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a sum-
mer exhaust fan. Close fireplace dampers.
d.
Place in operation
Follow the lighting/operating instructions. Adjust
thermostat so appliance will operate continuously.
Test for spillage
e.
5 minutes of main burner operation. Use the flame
of a match or candle.
f. After it has been determined that
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers,
and any other gas-burning appliance to their previ-
ous conditions of use.
Any improper operation of common venting system
should be corrected so the installation conforms with
the National Fuel Gas Code, ANSI Z223.1-latest edition.
Correct by resizing to approach the minimum size as
determined using the appropriate tables in Part 11 of
that code. Canadian installations must comply with
B149.1 or B149.2 Installation Code.
8
— Do not install the CGs-4E into a common vent with any other appliance. This will
in the common venting
for proper
— Insofar as is practical, close all
the appliance being inspected.
at draft hood relief opening after
each appliance
CGs-4E special vent system
Vent system
The CGs-4E boiler requires a special vent system, de-
signed for pressurized venting. Model CGs-4E is rated
ANSI Z21.13
Category IV
(pressurized vent, likely to
condense in the vent).
You may use any of the vent systems covered by the
CGs Venting Supplements included in the envelope as-
sembly. The CGs vent starter is a special item, designed
only for CGs and CGs-4E boilers, available from each
vendor. Do not attempt to connect the vent to the CGs-
4E boiler with any other means.
DO NOT
different systems. The vent system
could fail, causing leakage of flue
products into the living space.
Vent termination and combustion air
supply
The CGs-4E boiler may be vented through the roof or
through a side wall. Follow the appropriate vent supple-
ment for the vent system chosen. The maximum vent
length depends on boiler size. Refer to the vent supple-
ment to determine acceptable vent length.
Combustion air for the CGs-4E boiler must be ducted
directly to the boiler from outside. For outside air (direct
vent installation), two options are available for the flue/
air termination. The air supply must
at the same location as the flue, using either:
Vertical direct vent
1.
installation. Obtain the
Through-Roof or Through-Unused
Weil-McLain
Chimney
termination kit and supplement. Refer
Vertical Direct Venting
to
packed with the kit, and to the vent manufacturer's
instructions for the vent material chosen.
2.
Sidewall direct vent
installation. Use the
Intake
termination kit shipped with the boiler. Refer
CGs Direct Venting: Sidewall & Direct Exhaust
to
Venting: Vertical or Sidewall
shipped with the boiler.
Part number 550-110-282/1108
mix components from
ALWAYS
terminate
Venting Supplement,
Vent/Air
Venting Supplement