Daikin REYQ72 Serveice Manual page 53

R-410a heat recovery 60hz
Table of Contents

Advertisement

Basic Control
Compressor Operating Priority
Each compressor operates in the following order of priority.
REYQ72M
STEP
INV
1
52Hz
2
57Hz
3
62Hz
4
68Hz
5
74Hz
6
81Hz
7
88Hz
8
96Hz
9
104Hz
10
110Hz
11
116Hz
12
124Hz
13
133Hz
14
143Hz
15
158Hz
16
165Hz
17
177Hz
18
189Hz
19
202Hz
20
210Hz
21
52Hz
22
74Hz
23
96Hz
24
116Hz
25
133Hz
26
158Hz
27
177Hz
28
202Hz
29
210Hz
Compressors are operated in the order of descending priorities.
Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
"Master unit", and "slave unit" in this section are the names for control, and they will be transferred according to the
priority of rotation system.
42
REYQ72M
REYQ96M
No. 1 No. 2
No. 1 No. 2
INV
STD1
INV
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
INV:
Inverter compressor
STD1: Standard compressor 1
STD1
REYQ96M
STEP
INV
1
52Hz
2
57Hz
3
62Hz
4
68Hz
5
74Hz
6
81Hz
7
88Hz
8
96Hz
9
104Hz
10
110Hz
11
116Hz
12
124Hz
13
133Hz
14
143Hz
15
158Hz
16
165Hz
17
177Hz
18
189Hz
19
202Hz
20
210Hz
21
52Hz
22
74Hz
23
96Hz
24
116Hz
25
133Hz
26
158Hz
27
177Hz
28
202Hz
29
210Hz
SiUS39-602
STD1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
Function