Improper Combination Of Optional Controllers For Centralized Control; Ma" Improper Combination Of Optional Controllers For Centralized Control - Daikin REYQ72 Serveice Manual

R-410a heat recovery 60hz
Table of Contents

Advertisement

Troubleshooting (OP: Central Remote Controller)
" MA "
3.3
Improper Combination of Optional Controllers for
Centralized Control
MA
Remote
Controller
Display
Applicable
Central remote controller
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
Decision
When the remote control adapter is present.
Conditions
Supposed
Causes
196

Improper combination of optional controllers for centralized control

More than one master controller is connected
Defect of PC board of optional controller for centralized control
SiUS39-602
Troubleshooting