UPS Type
AUTOMATIC BYPASS SWITCH
The automatic switch provides transfer of the load to the utility voltage without any interruption of the supply. The transfer is
initiated by a signal from the output converter protection circuit in case of an overload or high temperature.
When the conditions return to normal the load is automatically transferred back to the output converter. The automatic bypass
switch can be disabled by the end-user.
Bypass voltage limits
Transfer transients
Frequency tracking range
Slew rate
BATTERY
Battery type
Nominal voltage (V) / capacity (Ah)
Number of batteries
Capacity of standard battery set
Battery recharge time
Battery service life
Battery discharging
Runtime in minutes
VA / Watts
1000 / 800
2000 / 1600
3000 / 2400
5000 / 4000
6000 / 4800
8000 / 6400
10000 / 8000
BATTERY EXTENSION PACKS
Sheet steel cubicle
Dimensions (hxwxd, mm)
Dimensions (hxwxd, inch)
Battery
Weight with battery (Kg)
Weight with battery (Lbs)
Battery pack A (voltage V / capacity Ah)
Total capacity (Ah)
Typical runtime, 100% / 50% load, min.
Number of packs required
Battery pack B (voltage V / capacity Ah)
Total capacity (Ah)
Typical runtime, 100% / 50% load, min.
Number of packs required
For more info see section 7.1
STEP-UP TRANSFORMER CABINET MOUNTED UNDERNEATH VSD2 (FOR LANPRO-U 5/6-11U ONLY)
Sheet steel cubicle
Dimensions (hxwxd, mm)
Dimensions (hxwxd, inch)
Weight (Kg)
Weight (Lbs)
LX: OPM_LPA_11U_5K0_10K_1US_V021
:
L5-11U
L6-11U
:
-15%, +10% of nominal
:
typically 2% mean deviation over one half cycle.
:
± 2/4/6% of nominal (user selectable)
:
max. 1Hz/sec or 5Hz/sec (user selectable)
:
Sealed and maintenance free
:
12/7
12/7
:
20
20
:
7Ah
7Ah
:
1.5 - 3 hours for 80% capacity
:
up to 6 years (depending on operating conditions)
:
self discharge current ≤ 0.35 mA
discharge end voltage of the battery depending on the actual load
10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA
When the UPS is in sleeping mode the inverter will be switched off, battery
charger and rectifier are in operation
:
60
60
:
40
40
:
18
18
:
10
10
:
-
8
:
-
-
:
-
-
:
VSDA1
:
537x313x590
:
21.1x12.3x23.2
:
240Vdc/7Ah or 240Vdc/14Ah
:
73 or 123
:
161 or 271
:
240/7
240/7
:
14
14
:
25/60
21/50
:
1
1
:
240/14
240/14
:
21
21
:
45/90
35/75
:
1
1
:
VSDT2 + VSD2
:
995x313x730
:
39.2x12.3x28.7
:
175 Kg
:
386 Lbs
40
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
GE Digital Energy
L8-11U
L10-11U
12/12
12/12
20
20
12Ah
12Ah
120
120
60
60
40
40
22
22
17
17
11
11
-
8
240/7
240/7
19
19
22/50
16/39
1
1
240/14
240/14
26
26
33/70
25/57
1
1

Hide quick links: