Advertisement

WARNING! Risk of Fire!
Comply with all minimum
clearances to combustibles as
specifi ed. Framing or fi nish-
ing material closer than the
minimums listed must be con-
structed entirely of non-com-
bustible materials (i.e., steel
studs, concrete board, etc).
Outdoor Lifestyles by Hearth & Home Technologies Inc. • Carolina • 4066-300 • Rev. Z • 11/13
12 in. (305 mm)
max. combustible
mantel depth
6 in.
(151 mm)
minimum - one side only.
Alcove installations require
14 in. (356 mm) from each side
of the firebox opening.
Figure 3.3
Clearances
Ceiling or
Overhang
(406 mm)
deep non-combustible
hearth extension recommended
when floor in front is combustible.
82 in.
(2083 mm)
minimum
height
49-1/2 in.
(1257 mm)
minimum
25 in.
(635 mm)
minimum
16 in.
9