Installing the Alarm Termination Box (ATB)

Installation

External
Power Supply
Relay Ratings
1A @ 30 VDC
0.5A @ 24 VAC
Rev 1.0
The ATB is shipped with the VideoBloX system and consists of a stainless steel box with a
ribbon cable.
Support for 32 Alarm Inputs - potential free (dry) contact
Support for 4 Form C Relays
Removable Terminal Blocks
1.
Connect the ATB to the VideoBloX CPU using the ribbon cable supplied.
2.
Connect a toggle switch or other alarm device to activate the alarm signal to Input #1
of ATB.
3.
Connect an output device (lamp or sounder) to the Common/Normally Open of
Output #1 and the appropriate power supply.
Figure 6
Alarm Terminal Block (ATB) Connections
Controlled
Device
RelayOutp ut s
Ribbon Connector
to CPU
ALARMTERMINATION BOX
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
OUT2
17
18
19
20
21
22
23
24
OUT3
OUT4
25
26
27
28
29
30
31
32
AlarmInput s
11
VideoBloX Quick Start Guide
Typical Input
NO/NC Dry Contact
Alarm Inputs are
pulled to 5 VDC by
10K resistor.