Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C Installation And Operation Manual

Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C Installation And Operation Manual

Heatcraft refrigeration products llc. home theater server - multi-room video controller user manual

Advertisement

H-IM-80C (
12/03)
Replaces H-IM-80B (12/02)
Beacon II Smart Controller
Installation & Operation
Manual
December, 2003

Table of Contents

Features ................................................................2-3
Installation .............................................................4
Wiring ....................................................................5
Power Supply ........................................................6
Button Functions ...................................................7
Locking Beacon II Smart Controller ...................... 10
Error Codes ...........................................................10
Wiring Errors .........................................................11
Alarm Codes .........................................................11
Alarm Buzzer .........................................................12
Data Logging .........................................................12
Smart Defrost ........................................................13
PC & Modem Access ............................................14
System Defaults ....................................................15
Parts List ...............................................................16
Operational Limits .................................................16
Diagnostics ............................................................17-20
Wiring Diagrams ....................................................21-23
Part No. 25000601

Advertisement

Table of Contents
loading

Summary of Contents for Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C

  • Page 1: Table Of Contents

    H-IM-80C ( 12/03) Replaces H-IM-80B (12/02) Beacon II Smart Controller Installation & Operation Manual December, 2003 Table of Contents Features ...2-3 Installation ...4 Wiring ...5 Power Supply ...6 Initialization of Beacon II Smart Controller ...7 Button Functions ...7 Programming Beacon II Smart Controller ... 8 Monitoring Beacon II Smart Controller ...
  • Page 2: Features

    Temperature, the Current Time of day and the Mode (i.e. COOL, DEFROST or OFF). When multiple systems are being controlled, the system number (i.e. SYS 1, SYS 2, SYS 3, SYS 4) will also be displayed on the LCD. © 2003, Heatcraft Refrigeration Products LLC...
  • Page 3 Beacon II Smart Controller Features Features of the Beacon II Smart Controller • Monitoring of the complete refrigeration system. • Programming of a variety of parameters for the optimum control of the refrigeration system. • The Beacon II Smart Controller has a Liquid Crystal Display (LCD) which shows: current time, actual box temperature, box temperature set-point and if there is an alarm or fault condition.
  • Page 4: Installation

    Installation INSTALLATION The Beacon II Smart Controller should be installed in a location where the large Liquid Crystal Display (LCD) can be viewed easily, yet is secure and vibration free. Because of the LCD screen, the Beacon II Smart Controller should not be mounted where it will experience temperatures below 40 F or above 100 F.
  • Page 5: Wiring

    WIRING All 24 volt wiring must be run separate from the line voltage wiring. All Low voltage wiring must be 18 gauge minimum and must be run separate from high voltage wiring. The maximum distance from the Beacon II Smart Controller to the Master Evaporator is 1000 ft.
  • Page 6: Power Supply

    For the second system, connect MULTI OUT 2 from the Beacon II Smart Controller to the MULTI IN on the Beacon II board on the Evaporator in this second system. Then connect MULTI IN 2 from the Beacon II Smart Controller to the MULTI OUT on the Beacon II board on the Evaporator on this second system.
  • Page 7: Initialization Of Beacon Ii Smart Controller

    Initialization of Beacon II Smart Controller will continue to operate and maintain the box temperature. This occurs only if an external power supply is used on the Beacon II Smart Controller. If the Beacon II Smart Controller LCD displays all 88888 this indicates that the power supply is below 18 VAC.
  • Page 8: Programming Beacon Ii Smart Controller

    Programming Beacon II Smart Controller • COOLING: Depressing this button will start the system in the cooling cycle immediately (The 4 minutes “Hold Off” is bypassed). This button will illuminate to indicate that the Cooling function is “ON”. System operation will be as described under REFRIGERATION MODE in the Beacon II installation manual.
  • Page 9: Monitoring Beacon Ii Smart Controller

    Monitoring With Beacon II Smart Controller SUPRHT • – Superheat: 4 to 20 F. Use “SETPOINT” slide-bar to select desired superheat temp., then press “ENTER.” If multiple evaporators are connected, use the “+” button to set other evaporators on this system. SMT DFT •...
  • Page 10: Locking Beacon Ii Smart Controller

    Locking Beacon II Smart Controller & Error Codes EXVSET • - Expansion valve step setting (Stepper Motor setting 0 to 255 steps: use + button to check other evaporators if Master/slave) SUCTMP • – Evaporator Suction temperature (Measured by the Suction Sensor) SSVTMP •...
  • Page 11: Wiring Errors

    Wiring Error & Alarm Codes *SPSEN - • Suction pressure transducer shorted, open or not installed *ODSEN - • Outdoor temperature sensor shorted *SUPLO - • Superheat too low *SHTDN - • Compressor shutdown (High or low refrigerant pressure or low oil pressure) The error code will flash alternately with the normal display information.
  • Page 12: Alarm Buzzer

    Alarm Buzzer & Data Logging The system will pumpdown, cycle off and try to restart for three consecutive times. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions. Oil pressure High pressure or low pressure cutout (or any other compressor safeties) After the third try, the Alarm contacts will be closed and an alarm message displayed on the LCD screen.
  • Page 13: Smart Defrost

    Real-time data can also be recorded and stored on a Desktop PC while the PC is connected to the Beacon II Smart Controller. The PC will continuously request information from the Beacon II Smart Controller regarding system operation and setup and record this data every minute, in an Excel spreadsheet.
  • Page 14: Pc & Modem Access

    PC And Modem Access PC & MODEM ACCESS For access to the system from a PC directly or via a modem, the SMART II Software must be purchased and installed on your PC. With PC access, ALL system settings can be monitored, changed or logged from a remote location.
  • Page 15: System Defaults

    SYSTEM DEFAULTS Following are factory defaults for the parameters which can be programmed in the Beacon II Smart Controller. If the user does not select a setting for any of the following parameters, the default will be used. It is important the user set ALL parameters based of their needs. PARAMETERS Refrigerant Box Temperature...
  • Page 16: Parts List

    Parts List PART DESCRIPTION Beacon II Control Board Temperature Sensor kit – White Leads* Transformer 120/24 volt – 40 VA Transformer 240/24 volt - 40 VA Transformer 460/24 volt – 40 VA Transformer 575/24 volt – 40 VA Pilot Relay Contactor for Compressor 40 amp with 24 volt Coil Terminal Block –...
  • Page 17: Diagnostics

    Beacon II Troubleshooting Guide PROBLEM Step ACTION ITEM Check Primary Power Supply Disconnect Check Voltage to Evaporator Transformer LED is not lit. Check Transformer Secondary Output Volts Check Voltage at Control Board (24V and C) Replace Control Board Check Compressor internal overloads Check Control Power to Condensing Unit LED shows Coo , but (24 Volts across “COMP”...
  • Page 18 Beacon II Troubleshooting Guide (continued) PROBLEM Step ACTION ITEM Check wiring connection to the board Low Pressure Safety (LPS) Tripped: • Check for correct refrigerant type • Check refrigerant charge • Check LPS setting • Check LPS wiring • Check EEV operation (stuck?) •...
  • Page 19 Beacon II Troubleshooting Guide (continued) PROBLEM Step ACTION ITEM Multi-out to Multi-in Check for 24 volts power to the board Communication Wiring (only shows after initial Check for crossed communication wiring successful connection) (multi-out not wired to multi-in terminals) Check for broken communication wiring (E9 continued) Master Communication Error...
  • Page 20: Diagnostics

    Beacon II Troubleshooting Guide (continued) PROBLEM Step ACTION ITEM Check system operation: Is it running? Check system charge Check for proper operating superheat Check for high superheat and EEV wide open Check Low Pressure Safety Switch Cannot get to box Compare equipment capacity with requirements temperature Check box temperature setpoint...
  • Page 21: Wiring Diagrams

    Wiring Diagrams...
  • Page 22 Wiring Diagrams...
  • Page 23: Wiring Diagrams

    Wiring Diagrams...
  • Page 24 Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice. Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd • Stone Mountain, GA 30087 (770) 465-5600 • Fax (770)465-5990 www.heatcraftrpd.com...