Differential Pressure Monitor Owner's Manual
Ordering Notes
Differential Pressure Monitor with Keyed
Switch for negative pressurization.
Differential Pressure Monitor with Keyed
Switch for positive pressurization.
Differential Pressure Monitor without
Keyed Switch.
Related Equipment
Remote Pressure Transmitter for use with
the Differential Pressure Monitor.
Calibration tool for Remote Pressure
Transmitter.
Hardware Inputs
Digital
•
Remote pressure transmitter (2 for App. 702 and 704, patient room and anteroom)
•
Door switch (optional)
Hardware Outputs
Analog
•
4-20 mA pressure signal
•
2-value resistive signal to identify pressurization mode to Room Pressurization
Controller
Digital
•
Alarm relay
•
2-state signal for pressurization mode to Constant Volume Controller
2
547-005
547-006
547-002
547-003
547-004
Siemens Building Technologies, Inc.