Heat & Glo EM-415 Owner's Manual page 23

Installation and operation
Hide thumbs Also See for EM-415:
Table of Contents

Advertisement

For installations utilizing an ST375 Square Termination
Cap the last chimney section must not be more than
4-1/2 in. (114 mm) below the chase top. See Figure 6.7.
Cap Standoff
1-1/2 in.
(38 mm) min.
overlap
Top of Pipe
Figure 6.7
Installing an ST375 Square Termination Cap
For installations utilizing a TS345/TS345P Square
Termination Cap, the uppermost chimney section must
not be more than 3 in. (76 mm) below the chase top. See
Figure 6.8
Flashing
Collar
1-1/2 in.
(38 mm)
Top of Pipe
min.
overlap
Figure 6.8
Installing a TS345/TS345P Square Termination Cap
Flashing Collar
2 in. (51 mm) min.
4-1/2 in.
(114 mm)
max.
2 in.
(51 mm)
min.
3 in.
(76 mm)
max.
Heat & Glo • EM-415/EM-415H • 31317 Rev Q • 10/06
For installations utilizing an TCT375 Terra Cotta Cap the last
chimney section must be between 7 in. (178 mm) below
the chase top and 2 in. (51 mm) above. See Figure 6.9.
1-1/2 in. (38 mm)
min. overlap
{
Top of Pipe
Figure 6.9
Installing a TCT375 Terra Cotta Cap
For chase installations you can use a TR344 Round
Termination Cap, a TR342 Round Telescoping Termination
Cap, an ST375, TS345 or TS345P Square Termination
Cap, or a TCT375 Terra Cotta Termination Cap.
For installations utilizing a European Copper Series
Termination Cap, See Figure 6.10.
Install termination caps following instructions provided
with them.
Cap Base
bracket (8)
screw (8)*
chimney top
chase
top
(metal or masonry)
SL pipe
inner flue
Figure 6.10 Installing a European Copper Series Termination Cap
(CT3-King shown)
The last section of pipe
must stop between the
distances given below.
2 in. (51 mm) above top
of the chase.
7 in. (178 mm) below top
of the chase.
(cap inner flue)
2 - 6 in.
(51-152 mm)
2 in. (51 mm)
typical
23