3.3.8 Guidelines for Selecting a 200V Power Distribution Box
AC200V Power Distribution Box Brief Specifications
n
U number
Voltage
1U
200V
0U
200V
Guidelines on the Number of AC200V Power Distribution Boxes
n
Model
2400E
2800E
2800E/2800B (*1) (4,500VA or less)
(*1) Calculate the required number of power distribution boxes according to the maximum apparent power. The maximum
apparent power can be calculated by using the Power Calculator ("Tool").
As the above example shows, if the maximum apparent power is 4.500VA or less , the number of power distribution boxes can
be reduced.
PRIMEQUEST 2000 Series Design Guide
Input
Output
NEMA L6-30P
IEC320 C19
NEMA L6-30P
IEC320 C19
200V non-redundant
configuration
1
2
1
3
24A/BOX
3
24A/BOX
200V redundant
configuration
1
2
2
100
Output current
16A per box
16A per box
200V dual power feed
configuration
2
4
2
Copyright 2014 FUJITSU LIMITED